Fireye NX6100 (Nexus) fault F15: Combustion air pressure detected when it should not be

Fireye NX6100 (Nexus)lockoutCommissioning Manual 1.4 (Section 5 issue 1pt4D)
Technical review pending. This guide is based on the cited manufacturer documentation; check it against the manual for your exact model and firmware before acting.

F15 means the main combustion air pressure switch registered air when the controller expected none. Subset 1 means air was seen at the wrong time; subset 2 means the switch still showed air more than three minutes after the burner turned off. The manual also notes F15 appears if the air-switch option (Opt 6.x) is not set.

Diagnose this with AI

Upload a keypad photo, the fault history or a parameter export from your Fireye NX6100 (Nexus). InduQT compares the evidence and suggests the next useful checks.

Try Free Boiler Diagnostic

When it happens

Reading the subset

SubsetWhat it tells you
1Air pressure registered when it should not be present
2Air pressure still registered more than 3 minutes after the burner turned off

Where it sits in the burner

Supervised function: Combustion air proving.

ComponentSignals to look atHow it fails
Combustion air proving switchCombustion air proving switch, Combustion air pressureWelded, jumpered or miswired contact; Pressure or position switch out of adjustment; Restricted combustion air path
Combustion air fan (FD / ID)Combustion fan running, Combustion fan speed, Combustion air pressure, Fan motor current, Fan vibrationRestricted combustion air path; Fan motor or drive fault; Bearing wear or misalignment
Burner management controllerBurner sequence state, Controller supply voltageConfiguration or commissioning data changed; Controller internal fault; Supply voltage, frequency or grounding problem; Electrical noise on signal wiring

Likely causes and checks

1Switch contacts stuck or a jumper left in

Points to it
Every start; switch reads closed with the fan stopped.
Check
Check the switch with the fan off and isolated; look for jumpers from previous work.

2Fan still running or windmilling (subset 2)

Points to it
Fan keeps turning after shutdown; shared breeching or strong stack draft.
Check
Confirm the fan stops; read pressure at the sensing point with the fan off.

3Option parameter not set

Points to it
New installation or after parameter changes.
Check
Have the commissioning engineer confirm the Opt 6.x air switch settings.

Telling it apart

Evidence to collect

Work on fuel trains, burners, pressure vessels and electrical equipment must be done by qualified personnel following the manufacturer’s documentation and local codes. Never bypass a safety device or interlock.