Fireye NX6100 (Nexus) fault F16: Second (primary) air pressure not detected

Fireye NX6100 (Nexus)lockoutCommissioning Manual 1.4 (Section 5 issue 1pt4D)
Technical review pending. This guide is based on the cited manufacturer documentation; check it against the manual for your exact model and firmware before acting.

Some burners have a second, primary air pressure switch as well as the main combustion air switch. F16 means that optional primary switch did not register air when the controller required it. The subset is the burner status number.

Diagnose this with AI

Upload a keypad photo, the fault history or a parameter export from your Fireye NX6100 (Nexus). InduQT compares the evidence and suggests the next useful checks.

Try Free Boiler Diagnostic

When it happens

Reading the subset

SubsetWhat it tells you
Burner status numberWhere in the sequence primary air was not proven

Where it sits in the burner

Supervised function: Combustion air proving.

ComponentSignals to look atHow it fails
Combustion air proving switchCombustion air proving switch, Combustion air pressurePressure or position switch out of adjustment; Restricted combustion air path; Welded, jumpered or miswired contact
Combustion air fan (FD / ID)Combustion fan running, Combustion fan speed, Combustion air pressure, Fan motor current, Fan vibrationRestricted combustion air path; Fan motor or drive fault; Bearing wear or misalignment

Likely causes and checks

1Primary air fan or path

Points to it
Primary air fan not running or restricted.
Check
Confirm the primary air source runs and its path is clear.

2Primary air switch setpoint or sensing line

Points to it
Air present but switch does not make.
Check
Measure the differential at the switch and compare with its setpoint.

Telling it apart

Evidence to collect

Work on fuel trains, burners, pressure vessels and electrical equipment must be done by qualified personnel following the manufacturer’s documentation and local codes. Never bypass a safety device or interlock.