Fireye NX6300 (Nexus) fault F11: False Flame

Fireye NX6300 (Nexus)lockoutFirmware 1.4
Technical review pending. This guide is based on the cited manufacturer documentation; check it against the manual for your exact model and firmware before acting.

F11 means the controller saw a flame signal when there should be no flame, for example before purge, during purge or after shutdown, or while a shuttered scanner’s shutter was closed. The controller cannot tell a real flame from a faulty signal, so it locks out.

Diagnose this with AI

Upload a keypad photo, the fault history or a parameter export from your Fireye NX6300 (Nexus). InduQT compares the evidence and suggests the next useful checks.

Try Free Boiler Diagnostic

When it happens

Reading the subset

SubsetWhat it tells you
1xxFlame 1 (the first flame input); the last two digits are the burner status number
2xxFlame 2 (the second flame input)
x01, x02Burner off or waiting to purge: flame seen at rest
x05 to x09During closed/air/purge position proving or pre-purge
x10Pre-ignition, with the igniter on but no fuel
x17, x18Post-purge, after the fuel valves closed

Where it sits in the burner

Supervised function: Flame supervision.

ComponentSignals to look atHow it fails
Flame scanner (UV / IR)Flame signalScanner no longer sighted on the flame root; Detector or amplifier ageing; Electrical noise on signal wiring; Dirty or fogged scanner sight path
Flame amplifier / flame inputFlame signalDetector or amplifier ageing; Electrical noise on signal wiring; Wrong detector, amplifier or configuration
Main safety shutoff valvesMain fuel valve output, Valve proof of closureValve seat leakage or slow closing; Fuel valve not opening fully; Welded, jumpered or miswired contact

Likely causes and checks

1Fuel still burning after shutdown (subset x17–x18 or x01)

Points to it
Visible flame after the cycle; oil after-drip or leaking safety valve.
Check
Look into the furnace. If flame persists, close the manual fuel valves and have the safety shutoff valves tightness-tested; the valve leak test (if fitted) helps here.

2Detector seeing ignition spark (subset x10)

Points to it
Only at pre-ignition when the spark starts.
Check
Re-sight the scanner so it cannot view the spark; check scanner and ignition cable routing.

3Failing UV tube or self-check detector

Points to it
Signal in a dark, cold furnace; often accompanied by F66 events.
Check
Cover the scanner with the burner off; any remaining signal means a detector or input fault.

4Noise pickup on the flame input

Points to it
Intermittent, coinciding with motor or ignition switching.
Check
Check screen termination and separation of the scanner cable from power and ignition wiring.

Telling it apart

Evidence to collect

Work on fuel trains, burners, pressure vessels and electrical equipment must be done by qualified personnel following the manufacturer’s documentation and local codes. Never bypass a safety device or interlock.