Honeywell 7800 Series troubleshooting

Honeywell
Technical review pending. This guide is based on the cited manufacturer documentation; check it against the manual for your exact model and firmware before acting.

The Honeywell 7800 Series is a family of microprocessor burner control relay modules, such as the RM7800, usually fitted with the S7800 Keyboard Display Module. On a lockout the display shows a numbered fault code, a message and the sequence step the burner was in, which together narrow down the cause.

Diagnose this with AI

Upload a photo of the alarm screen, the fault history or a data export. InduQT compares the evidence and suggests the next useful checks.

Try Free Boiler Diagnostic

How it reports faults

Operating sequence

  1. INITIATE / STANDBYThe module checks itself and waits for a call for heat; limits and interlocks must be proven.
  2. PURGECombustion air purges the furnace; the airflow interlock must be proven.
  3. PILOT IGN (PFEP)Pilot Flame Establishing Period: the igniter and pilot valve are energised and flame must be proven.
  4. MAIN IGN (MFEP)Main Flame Establishing Period: the main fuel valve opens and main flame must be proven.
  5. RUNThe burner fires under its modulation control with flame supervised.
  6. POSTPURGEAir purges the furnace after the burner shuts down.

Fault codes

CodeName
13*Airflow Sw. On*: airflow interlock fault during STANDBY
16*Flame-Out Timer*: no flame detected during PFEP
17*Main Flame Fail*: main flame lost in RUN after at least 10 s
19*Main Flame Ign.*: flame lost during MFEP or the first 10 s of RUN
23*Airflow Switch*: airflow interlock fault during PREPURGE
28*Pilot Flame Fail*: pilot flame failure
32*Airflow Switch*: combustion airflow interlock fault

Evidence to collect

Work on fuel trains, burners, pressure vessels and electrical equipment must be done by qualified personnel following the manufacturer’s documentation and local codes. Never bypass a safety device or interlock.