Fireye NX6100 (Nexus) fault F43: Gas pressure limit exceeded, or sensor fault

Fireye NX6100 (Nexus)lockoutCommissioning Manual 1.4 (Section 5 issue 1pt4D)
Technical review pending. This guide is based on the cited manufacturer documentation; check it against the manual for your exact model and firmware before acting.

F43 means the controller’s own gas pressure sensor reads outside the operating limits set for the burner, or the sensor stopped responding. The subset separates low pressure, high pressure and sensor faults.

Diagnose this with AI

Upload a keypad photo, the fault history or a parameter export from your Fireye NX6100 (Nexus). InduQT compares the evidence and suggests the next useful checks.

Try Free Boiler Diagnostic

When it happens

Reading the subset

SubsetWhat it tells you
1Pressure too low
2Pressure too high
10Gas pressure sensor not responding correctly
255CANbus connection fault

Where it sits in the burner

Supervised function: Main fuel delivery.

ComponentSignals to look atHow it fails
Fuel supply and regulatorMain gas pressure, Oil pressureFuel supply pressure droop; Regulator out of adjustment or sticking
Controller communication networkBurner sequence stateCommunication wiring fault; Electrical noise on signal wiring

Likely causes and checks

1Supply pressure low (subset 1)

Points to it
At high fire or when other users start; utility or plant supply issue.
Check
Check supply pressure upstream of the burner regulator; the manual’s first instruction is to check the gas supply pressure.

2Regulator lock-up or creep (subset 2)

Points to it
High pressure at light-off or after shutdown.
Check
Have the regulator inspected for lock-up and creep.

3Sensor or CANbus (subset 10 or 255)

Points to it
Reading jumps or is missing.
Check
Check the sensor and its CANbus wiring.

Telling it apart

Evidence to collect

Work on fuel trains, burners, pressure vessels and electrical equipment must be done by qualified personnel following the manufacturer’s documentation and local codes. Never bypass a safety device or interlock.