Honeywell 7800 Series fault 13: Airflow Sw. On

Honeywell 7800 Serieslockout
Technical review pending. This guide is based on the cited manufacturer documentation; check it against the manual for your exact model and firmware before acting.

In STANDBY the relay module expects the combustion airflow interlock to be open, because the fan has not been asked to run. Fault 13 means the module saw that circuit closed at a point where no air flow should exist, so it cannot trust the switch to prove air during purge.

Diagnose this with AI

Upload a keypad photo, the fault history or a parameter export from your Honeywell 7800 Series. InduQT compares the evidence and suggests the next useful checks.

Try Free Boiler Diagnostic

When it happens

Where it sits in the burner

Supervised functions: Combustion air proving, Limit and interlock supervision.

ComponentSignals to look atHow it fails
Combustion air proving switchCombustion air proving switch, Combustion air pressurePressure or position switch out of adjustment; Welded, jumpered or miswired contact; Restricted combustion air path
Combustion air fan (FD / ID)Combustion fan running, Combustion fan speed, Combustion air pressure, Fan motor current, Fan vibrationRestricted combustion air path; Fan motor or drive fault; Bearing wear or misalignment
Burner management controllerBurner sequence state, Controller supply voltageController internal fault; Supply voltage, frequency or grounding problem; Configuration or commissioning data changed; Electrical noise on signal wiring

Likely causes and checks

1Air switch contacts stuck or welded closed

Points to it
Fault appears on every start; the switch reads closed with the fan stopped.
Check
With the fan stopped and power isolated, check the switch contacts for continuity and inspect for a jumper left from previous work.

2Air still moving through the boiler with the fan off

Points to it
Intermittent, worse in windy weather, with a tall stack or when another fan shares the breeching.
Check
Read the pressure at the switch sensing point with the fan off; compare with the switch setpoint and the burner maker’s draft limits.

3Fan running when it should be off

Points to it
Fan can be heard in STANDBY; motor contactor or fan VSD stays on.
Check
Check the fan contactor, starter auxiliaries and any VSD run command; confirm the fan stops when the module drops the motor output.

4Wiring error feeding the airflow input

Points to it
Line voltage present on the interlock input with the switch open.
Check
Table 3 groups 11, 12 and 13 together and directs a voltage check on the interlock terminals with the controller off; a qualified technician should trace any unexpected feed.

Telling it apart

Evidence to collect

Work on fuel trains, burners, pressure vessels and electrical equipment must be done by qualified personnel following the manufacturer’s documentation and local codes. Never bypass a safety device or interlock.