Honeywell 7800 Series fault 16: Flame-Out Timer

Honeywell 7800 Serieslockout
Technical review pending. This guide is based on the cited manufacturer documentation; check it against the manual for your exact model and firmware before acting.

During the Pilot Flame Establishing Period (PFEP) the module energises the igniter and pilot valve and expects the flame detector to prove a pilot flame before the period ends. Fault 16 means the period expired without a usable flame signal, so the main valves never opened.

Diagnose this with AI

Upload a keypad photo, the fault history or a parameter export from your Honeywell 7800 Series. InduQT compares the evidence and suggests the next useful checks.

Try Free Boiler Diagnostic

When it happens

Where it sits in the burner

Supervised functions: Ignition and pilot, Flame supervision.

ComponentSignals to look atHow it fails
Ignition transformer and electrodeIgnition outputIgniter electrode wear or wrong gap; Ignition transformer or lead failure
Pilot gas trainPilot valve output, Pilot gas pressureFuel valve not opening fully; Regulator out of adjustment or sticking; Fuel supply pressure droop
Flame scanner (UV / IR)Flame signalScanner no longer sighted on the flame root; Dirty or fogged scanner sight path; Detector or amplifier ageing; Electrical noise on signal wiring
Flame amplifier / flame inputFlame signalWrong detector, amplifier or configuration; Detector or amplifier ageing; Electrical noise on signal wiring
Air damper, actuator and linkageAir damper position, Firing rateAir/fuel ratio drift; Damper or valve linkage slip; Actuator or feedback fault

Likely causes and checks

1No spark or a weak spark

Points to it
No ignition sound or visible spark through the sight glass.
Check
Inspect the electrode tip, insulator and gap; check the transformer output and high-voltage lead per the burner manual.

2Pilot gas not arriving

Points to it
Spark present but no pilot flame; pilot regulator or valve recently serviced.
Check
Read pilot gas pressure during the trial; confirm the pilot valve opens and the manual pilot cock is open.

3Detector does not see the pilot

Points to it
Pilot visible but flame signal stays below the minimum.
Check
Measure the flame signal at the test jack during the pilot trial. The checkout publication uses 1.25 Vdc as the minimum flame signal for a reliable pilot or main flame on the 7800 test jack (65-0229-2, Flame signal and pilot turndown tests). Clean and re-sight the scanner, or check flame rod position.

4Amplifier and detector not compatible

Points to it
After a detector or amplifier was replaced.
Check
Confirm the plug-in amplifier type matches the detector, as Table 3 directs.

5Too much light-off air

Points to it
Pilot lights then blows out; after damper or low-fire position work.
Check
Check the light-off damper position against the commissioning record.

Telling it apart

Evidence to collect

Work on fuel trains, burners, pressure vessels and electrical equipment must be done by qualified personnel following the manufacturer’s documentation and local codes. Never bypass a safety device or interlock.