Honeywell 7800 Series fault 33: Pre-Ignition ILK

Honeywell 7800 Serieslockout
Technical review pending. This guide is based on the cited manufacturer documentation; check it against the manual for your exact model and firmware before acting.

The pre-ignition interlock is usually the proof-of-closure switch on the safety shutoff valves. Fault 33 means the module did not see it proven when required, so it cannot confirm the fuel valves are shut before purge or ignition.

Diagnose this with AI

Upload a keypad photo, the fault history or a parameter export from your Honeywell 7800 Series. InduQT compares the evidence and suggests the next useful checks.

Try Free Boiler Diagnostic

When it happens

Where it sits in the burner

Supervised function: Valve proving and proof of closure.

ComponentSignals to look atHow it fails
Main safety shutoff valvesMain fuel valve output, Valve proof of closureValve seat leakage or slow closing; Fuel valve not opening fully; Welded, jumpered or miswired contact

Likely causes and checks

1Valve closing slowly

Points to it
Fault appears just after a shutdown; valve actuator sluggish.
Check
Table 3 states the valve must close within five seconds; time the valve closing and service or replace the actuator.

2Proof-of-closure switch out of adjustment or failed

Points to it
Valve closes fully but the switch does not make.
Check
Check the POC switch contacts and adjustment per the valve maker; confirm line voltage at the pre-ignition interlock input in STANDBY.

Telling it apart

Evidence to collect

Work on fuel trains, burners, pressure vessels and electrical equipment must be done by qualified personnel following the manufacturer’s documentation and local codes. Never bypass a safety device or interlock.