Honeywell 7800 Series fault 15: Flame Detected

Honeywell 7800 Serieslockout
Technical review pending. This guide is based on the cited manufacturer documentation; check it against the manual for your exact model and firmware before acting.

The relay module checks for flame before every start. Fault 15 means it saw a flame signal during STANDBY. Either fuel is still burning in the furnace, or the detector, amplifier or wiring is producing a signal without a flame. Both are treated as unsafe, so the module locks out.

Diagnose this with AI

Upload a keypad photo, the fault history or a parameter export from your Honeywell 7800 Series. InduQT compares the evidence and suggests the next useful checks.

Try Free Boiler Diagnostic

When it happens

Where it sits in the burner

Supervised function: Flame supervision.

ComponentSignals to look atHow it fails
Flame scanner (UV / IR)Flame signalScanner no longer sighted on the flame root; Detector or amplifier ageing; Electrical noise on signal wiring; Dirty or fogged scanner sight path
Flame amplifier / flame inputFlame signalDetector or amplifier ageing; Electrical noise on signal wiring; Wrong detector, amplifier or configuration
Main safety shutoff valvesMain fuel valve output, Valve proof of closureValve seat leakage or slow closing; Fuel valve not opening fully; Welded, jumpered or miswired contact

Likely causes and checks

1Real flame after shutdown

Points to it
Flame visible through the sight glass after the cycle ends; burning oil drips or a leaking valve.
Check
Look into the furnace; if flame persists, close manual fuel valves and have the safety shutoff valves tightness-tested.

2Infrared scanner seeing hot refractory

Points to it
Only after long high-fire runs; IR detector; clears once the furnace cools.
Check
The checkout publication warns that IR detectors can respond to hot refractory; re-sight the scanner so it sees the flame, not glowing brick.

3Failed UV tube or amplifier

Points to it
Flame signal present in a cold, dark furnace; amplifier is old or a non-self-checking type.
Check
Measure the flame signal with the burner off and the scanner covered; replace the detector or amplifier if a signal remains.

4Noise on the flame lead

Points to it
Signal flickers with ignition or nearby motor starts; detector wires share conduit with power wiring.
Check
Route the flame detector leads separately from ignition and power wiring as Table 3 directs.

Telling it apart

Evidence to collect

Work on fuel trains, burners, pressure vessels and electrical equipment must be done by qualified personnel following the manufacturer’s documentation and local codes. Never bypass a safety device or interlock.