Honeywell 7800 Series fault 17: Main Flame Fail

Honeywell 7800 Serieslockout
Technical review pending. This guide is based on the cited manufacturer documentation; check it against the manual for your exact model and firmware before acting.

Fault 17 means the burner lit and ran normally, then the flame signal dropped out during RUN, at least 10 seconds after the main flame was established. Because light-off succeeded, look for something that changes while firing: fuel pressure, air flow, firing rate or the detector’s view of the flame.

Diagnose this with AI

Upload a keypad photo, the fault history or a parameter export from your Honeywell 7800 Series. InduQT compares the evidence and suggests the next useful checks.

Try Free Boiler Diagnostic

When it happens

Where it sits in the burner

Supervised functions: Flame supervision, Main fuel delivery, Firing-rate positioning.

ComponentSignals to look atHow it fails
Fuel supply and regulatorMain gas pressure, Oil pressureFuel supply pressure droop; Regulator out of adjustment or sticking
Main safety shutoff valvesMain fuel valve output, Valve proof of closureFuel valve not opening fully; Valve seat leakage or slow closing; Welded, jumpered or miswired contact
Flame scanner (UV / IR)Flame signalScanner no longer sighted on the flame root; Dirty or fogged scanner sight path; Detector or amplifier ageing; Electrical noise on signal wiring
Air damper, actuator and linkageAir damper position, Firing rateAir/fuel ratio drift; Damper or valve linkage slip; Actuator or feedback fault
Fuel valve actuator and linkageFuel valve position, Firing rateAir/fuel ratio drift; Damper or valve linkage slip; Actuator or feedback fault

Likely causes and checks

1Fuel pressure dips while firing

Points to it
Trips at high fire or when another large gas user starts; low gas pressure events near the trip.
Check
Trend burner gas (or oil) pressure across a full modulation cycle; compare with the burner’s required pressure at high fire.

2Main valve partially closing or chattering

Points to it
Valve actuator noise, voltage dips on the valve circuit, or a trip that coincides with vibration.
Check
Inspect main valve wiring and terminations; check the valve actuator and supply voltage during firing.

3Detector loses sight of the flame at some firing rates

Points to it
Flame signal good at low fire but weak at high fire, or the reverse.
Check
Record the flame signal at low fire, high fire and while modulating, as the checkout publication suggests. The checkout publication uses 1.25 Vdc as the minimum flame signal for a reliable pilot or main flame on the 7800 test jack (65-0229-2, Flame signal and pilot turndown tests).

4Air/fuel ratio drift makes the flame unstable

Points to it
Trips follow a tune-up, linkage work or seasonal air temperature change; flame looks lifting or smoky.
Check
Combustion-test across the firing range and check linkage for slip.

Telling it apart

Evidence to collect

Work on fuel trains, burners, pressure vessels and electrical equipment must be done by qualified personnel following the manufacturer’s documentation and local codes. Never bypass a safety device or interlock.