FANUC Series 0i-F / 0i-F Plus alarm PS0090: REFERENCE RETURN INCOMPLETE

FANUC Series 0i-F / 0i-F PlusfaultChecked against Series 0i-MODEL F documentation (B-64607EN/01)
Technical review pending. This guide is based on the cited manufacturer documentation; check it against the manual for your exact model and firmware before acting.

PS0090 (REFERENCE RETURN INCOMPLETE) on a FANUC 0i-F means the reference position return could not be completed normally. FANUC gives two cases: the return started too close to the reference position or ran too slowly, or an attempt was made to set the zero point of an absolute position detector when it could not yet be set.

Diagnose this with AI

Upload a keypad photo, the fault history or a parameter export from your FANUC Series 0i-F / 0i-F Plus. InduQT compares the evidence and suggests the next useful checks.

Try Free CNC Alarm Diagnostic

When it happens

Likely causes and checks

1Start point too close to the reference position

Points to it
Axis was parked near home before the return; works if moved away first.
Check
Jog the axis well away from the reference position and repeat. FANUC’s related DS0405 text asks for at least 2 motor revolutions between the start and the zero point.

2Reference return speed too slow

Points to it
Feedrate override low, or return feedrates recently changed.
Check
Check the override and the return feedrates (parameters 1428 and 1425) against the builder’s backup.

3Absolute detector zero point cannot be set yet

Points to it
Axis uses an absolute Pulsecoder and DS0300 was showing; setting the zero point fails.
Check
Follow FANUC’s remedy: rotate the motor at least one turn, switch the CNC and servo amplifier off and on, then set the zero position again.

4Deceleration dog or switch problem (dog-type return)

Points to it
Axis does not slow down at the dog, or the alarm repeats from a good start position.
Check
Check the deceleration dog and switch signal with the machine builder’s ladder/I/O diagnostics.

Telling it apart

Relevant parameters

ParameterNameWhy it matters
1425FL rate of the reference position returnSlow speed after the deceleration dog.
1428Reference return feedrate before a reference is establishedReturn speed before the first reference return.
1005#0 (ZRN)Alarm on automatic operation without reference return0: PS0224 if automatic operation starts without a reference return.
1005#1 (DLZ)Reference setting without dogsEnabled on dogless axes.

Evidence to collect

Work on fuel trains, burners, pressure vessels and electrical equipment must be done by qualified personnel following the manufacturer’s documentation and local codes. Never bypass a safety device or interlock.