FANUC Series 0i-F / 0i-F Plus alarm SV0411: EXCESS ERROR (MOVING)

FANUC Series 0i-F / 0i-F PlusfaultChecked against Series 0i-MODEL F documentation (B-64607EN/01)
Technical review pending. This guide is based on the cited manufacturer documentation; check it against the manual for your exact model and firmware before acting.

SV0411 (EXCESS ERROR (MOVING)) on a FANUC 0i-F means the positional deviation of an axis while it was moving became larger than the limit in parameter 1828. The motor could not keep up with the commanded motion, so the control stopped it.

Diagnose this with AI

Upload a keypad photo, the fault history or a parameter export from your FANUC Series 0i-F / 0i-F Plus. InduQT compares the evidence and suggests the next useful checks.

Try Free CNC Alarm Diagnostic

When it happens

Likely causes and checks

1Mechanical binding or a crash

Points to it
One axis only; alarm at the same position each time, or after a collision; jogging slowly is rough or noisy.
Check
With the axis isolated and locked out, check that the ballscrew, coupling and ways move freely and that way covers are not jammed with chips.

2Motor brake not releasing

Points to it
Vertical or braked axis; alarm right at the start of the first move after servo-on.
Check
Check that the brake releases when servo is enabled (brake supply and wiring per the machine builder’s diagram).

3Power or feedback cable fault

Points to it
Intermittent, sometimes only at certain axis positions where the cable flexes; may alternate with Pulsecoder alarms (SV0368, SV0446).
Check
Inspect and test the motor power and Pulsecoder cables; insulation-test the power cable and motor with them disconnected from the amplifier.

4Load or acceleration beyond the motor’s capability

Points to it
Only in heavy cuts or fast rapids; no fault found with the mechanics.
Check
Compare DGN 300 during the move with the 1828 setting; review feedrate, acceleration and cutting conditions.

5Parameter mismatch

Points to it
Alarm started after a parameter load, motor change or change of rapid rate or loop gain.
Check
Compare 1828, 1825 and the rapid rate with the builder’s backup; FANUC’s guideline sets 1828 from the rapid rate and servo loop gain with a margin of about 1.2.

Telling it apart

Relevant parameters

ParameterNameWhy it matters
1828Positioning deviation limit in movementLimit for SV0411. FANUC’s setting guideline is the rapid-traverse position error (rapid rate ÷ (60 × servo loop gain) ÷ detection unit) with a margin of about 1.2.
DGN 300 (diagnosis)Position error of each axisLive position error in detection units. FANUC gives position error = feedrate [mm/min] × 100 / (60 × servo loop gain) × 1/detection unit, with servo loop gain from parameter 1825 in 0.01 s⁻¹.
1825Servo loop gain for each axisIn 0.01 s⁻¹; FANUC lists 3000 as the usual value. Sets how much position error a given feedrate produces.

Evidence to collect

Work on fuel trains, burners, pressure vessels and electrical equipment must be done by qualified personnel following the manufacturer’s documentation and local codes. Never bypass a safety device or interlock.