Danfoss VLT AutomationDrive FC 302 fault A29: Heat Sink Temp

Danfoss VLT AutomationDrive FC 302faultOperating Guide for software 8.43; Programming Guide for software 9.5x / 48.96
Technical review pending. This guide is based on the cited manufacturer documentation; check it against the manual for your exact model and firmware before acting.

Alarm 29 on a Danfoss VLT FC 302 is Heat Sink Temp: the maximum heat sink temperature was exceeded. The alarm does not reset until the heat sink cools below a defined temperature, and the trip and reset points depend on drive power size.

Diagnose this with AI

Upload a keypad photo, the fault history or a parameter export from your Danfoss VLT AutomationDrive FC 302. InduQT compares the evidence and suggests the next useful checks.

Try Free Drive Diagnostic

When it happens

Likely causes and checks

1Heat sink fan damaged or not running

Points to it
Warning 23 or 24 fan fault logged; trips sooner than before.
Check
Cycle power and check the fan runs briefly at start-up; check fan operation (14-53 Fan Monitor supervises it).

2Dirty heat sink or blocked airflow

Points to it
Dusty site; filters or fins clogged; drive mounted with too little clearance.
Check
Inspect and clean the heat sink and check airflow clearance above and below the drive.

3Ambient temperature too high

Points to it
Trips cluster on hot afternoons; cabinet interior hot.
Check
Measure cabinet air temperature near the drive and compare with the drive’s rated ambient.

4Motor cables too long

Points to it
Long motor cable run; drive runs hot even at moderate load.
Check
Check motor cable length against the limits in the Operating Guide; Danfoss lists long cables as a cause.

Telling it apart

Relevant parameters

ParameterNameWhy it matters
14-53Fan MonitorFan fault warnings 23/24; do not disable it to hide a failed fan.

Evidence to collect

Work on fuel trains, burners, pressure vessels and electrical equipment must be done by qualified personnel following the manufacturer’s documentation and local codes. Never bypass a safety device or interlock.