Yaskawa GA500 fault oL1: Motor Overload
Fault oL1 on a Yaskawa GA500 is Motor Overload: the drive’s electronic thermal motor protection tripped. It can only be reset once U4-16 [Motor oL1 Level] is below 100. Yaskawa lists high load, short cycle times, low-speed running, a wrong L1-01 setting, a V/f pattern that does not suit the motor and a wrong base frequency.
Diagnose this with AI
Try Free Drive Diagnostic Upload a keypad photo, the fault history or a parameter export from your Yaskawa GA500. InduQT compares the evidence and suggests the next useful checks.
When it happens
- Constant speed under sustained heavy load
- Frequent starts and stops
- Long running at low speed on a general-purpose motor
Likely causes and checks
1Load too large
- Points to it
- Trips after running a while; output current above motor FLA.
- Check
- Measure output current and compare with the motor nameplate; decrease the load.
2Motor rated current or base frequency set wrong
- Points to it
- Trips at normal load after commissioning.
- Check
- Set E2-01 [Motor Rated Current (FLA)] and E1-06 [Base Frequency] to the motor nameplate values.
3Low-speed operation of a self-cooled motor
- Points to it
- Trips only during long low-speed running.
- Check
- Increase speed or reduce load at low speed, or use a drive-dedicated motor with L1-01 set to match.
4Acceleration/deceleration or cycle times too short
- Points to it
- Trips on machines that start and stop frequently.
- Check
- Review cycle times and increase C1-01 to C1-08.
5V/f pattern voltage too high
- Points to it
- High current at low speed with light load in V/f control.
- Check
- Adjust E1-04 to E1-10; the manual notes lowering E1-08 and E1-10 too far reduces low-speed overload tolerance.
6One drive running several motors
- Points to it
- Multiple motors on one drive output.
- Check
- Set L1-01 = 0 and fit a thermal overload relay to each motor, per the manual.
Telling it apart
- oL1 is the motor’s time-based overload. oL2 is the drive’s overload. oC is the instant overcurrent. oH3/oH4 come from a motor PTC thermistor input.
- V1000 equivalence: the V1000 manual lists oL1 Motor Overload with the same reset condition (U4-16 below 100) and the same L1-01, E2-01, E1-06 and V/f checks.
Relevant parameters
| Parameter | Name | Why it matters |
|---|---|---|
| E2-01 | Motor Rated Current (FLA) | Set from the motor nameplate. |
| L1-01 | Motor Overload (oL1) Protection | Selects the motor type; 0 disables (only with external relays). |
| U4-16 | Motor oL1 Level | Must be below 100 before oL1 can be reset. |
| E1-06 | Base Frequency | Set to the motor rated frequency. |
Evidence to collect
- U2-05 output current at fault and U4-16
- E2-01, E1-06 and L1-01 settings against the nameplate
- Duty cycle and running speed
- Motor temperature and cooling
Work on fuel trains, burners, pressure vessels and electrical equipment must be done by qualified personnel following the manufacturer’s documentation and local codes. Never bypass a safety device or interlock.