Yaskawa GA500 fault oC: Overcurrent

Yaskawa GA500fault
Technical review pending. This guide is based on the cited manufacturer documentation; check it against the manual for your exact model and firmware before acting.

Fault oC on a Yaskawa GA500 is Overcurrent: the drive sensors detected output current above the specified overcurrent detection level. Yaskawa lists heavy load, damaged motor insulation, shorted or grounded motor cable, short acceleration time, wrong V/f pattern, high torque compensation and starting onto a coasting motor among the causes.

Diagnose this with AI

Upload a keypad photo, the fault history or a parameter export from your Yaskawa GA500. InduQT compares the evidence and suggests the next useful checks.

Try Free Drive Diagnostic

When it happens

Likely causes and checks

1Motor cable short or ground, or damaged motor insulation

Points to it
Trips the instant the drive runs, even unloaded; may alternate with GF or SC.
Check
Disconnect the motor at the drive and megger cable and motor; measure cable-to-ground resistance as the manual directs.

2Acceleration time too short for the inertia

Points to it
Trips partway through the ramp; heavier loads trip sooner.
Check
Increase C1-01 (or C1-03/C1-05/C1-07) and the S-curve C2-01 to C2-04, then compare U2-05 output current at fault.

3Run command while the motor is coasting

Points to it
Trips at restart on fans or flywheels that are still turning.
Check
Set b3-01 = 1 (speed search at start) or start only after the motor has stopped.

4V/f pattern or torque compensation too high

Points to it
Trips at low speed with little load in V/f mode.
Check
Check E1-04 to E1-10 against the motor and reduce C4-01 [Torque Compensation Gain].

5Output contactor switching while the drive outputs voltage

Points to it
Trips coincide with a contactor between drive and motor operating.
Check
Change the sequence so the contactor does not switch while the drive is outputting voltage.

6Load too heavy or drive undersized

Points to it
Measured current above the drive rating; motor larger than the drive’s maximum applicable motor.
Check
Measure motor current and compare with the drive and motor nameplate ratings.

Telling it apart

Relevant parameters

ParameterNameWhy it matters
C1-01Acceleration Time 1Default 10.0 s; C1-03/C1-05/C1-07 are alternates.
C2-01 to C2-04S-Curve CharacteristicsSoftens the start and end of the ramp.
C4-01Torque Compensation GainReduce if excessive.
b3-01Speed Search at Start Selection1 = enabled; for starting onto a coasting motor.
C6-02Carrier Frequency SelectionLower it when the motor cable is long, per the manual.

Evidence to collect

Work on fuel trains, burners, pressure vessels and electrical equipment must be done by qualified personnel following the manufacturer’s documentation and local codes. Never bypass a safety device or interlock.