Yaskawa GA500 fault ov: Overvoltage

Yaskawa GA500fault
Technical review pending. This guide is based on the cited manufacturer documentation; check it against the manual for your exact model and firmware before acting.

Fault ov on a Yaskawa GA500 is Overvoltage: the DC bus voltage rose above the ov detection level while the drive was running, approximately 410 V for 200 V class drives and 820 V for 400 V class drives. The usual cause is regenerated energy from a deceleration that is too short.

Diagnose this with AI

Upload a keypad photo, the fault history or a parameter export from your Yaskawa GA500. InduQT compares the evidence and suggests the next useful checks.

Try Free Drive Diagnostic

When it happens

Likely causes and checks

1Deceleration time too short

Points to it
Trips only while slowing down; U2-08 DC bus at fault is high.
Check
Increase C1-02 (or C1-04/C1-06/C1-08), connect a dynamic braking option, or run Deceleration Rate Tuning.

2Stall prevention during decel set wrong

Points to it
L3-04 set for a braking resistor that is not fitted, or the reverse.
Check
Check L3-04 [Stall Prevention during Decel]; the manual gives 0 with a braking option and 3 if ov occurs with a DB resistor.

3Speed overshoot at the end of acceleration

Points to it
Trips just after reaching speed on a fast ramp.
Check
Increase C1-01 and C2-02 [S-Curve Time @ End of Accel], or set L3-11 = 1 [Overvoltage Suppression].

4Braking resistor wiring wrong or braking load too large

Points to it
Resistor fitted but trips continue.
Check
Check the braking resistor or unit wiring and its sizing for the braking load.

5Supply surges or high supply voltage

Points to it
Trips at constant speed; phase-advancing capacitors or thyristor converters share the supply.
Check
Measure the supply; Yaskawa suggests a DC link choke for surges.

6Ground fault in output cable or motor

Points to it
ov together with GF or oC history.
Check
Inspect and megger the motor cable, terminals and terminal box with the motor disconnected.

Telling it apart

Relevant parameters

ParameterNameWhy it matters
C1-02Deceleration Time 1Default 10.0 s; C1-04/C1-06/C1-08 are alternates.
L3-04Stall Prevention during DecelDefault 1; set 0 with a dynamic braking option.
L3-11Overvoltage Suppression Select1 = enabled; default 0.
L5-08Fault Reset Enable Select Grp2Controls whether auto restart applies to ov.

Evidence to collect

Work on fuel trains, burners, pressure vessels and electrical equipment must be done by qualified personnel following the manufacturer’s documentation and local codes. Never bypass a safety device or interlock.