Servo vibration or hum at standstill

Technical review pending. This guide is based on the cited manufacturer documentation; check it against the manual for your exact model and firmware before acting.

A servo that hums, buzzes or hunts while it is supposed to be holding still is almost always a tuning problem: loop gains set higher than the mechanics can support, an inertia ratio setting that does not match the real load, or a machine resonance the filters do not cover. Loose couplings, backlash and worn mechanics make all three worse.

Diagnose this with AI

Upload a photo of the alarm screen, the fault history or a data export. InduQT compares the evidence and suggests the next useful checks.

Try Free Servo Diagnostic

Where it shows up

Likely causes and how to tell them apart

1Loop gains too high

Points to it
Steady buzz, often around 200 to 400 Hz; started after a tuning change.
Check
Compare speed loop gain, position loop gain and integral time with defaults (Yaskawa Pn100 Kv 40.0 Hz, Pn102 Kp 40.0/s, Pn101 Ti 20.0 ms) and reduce them, or rerun autotuning.

2Inertia ratio setting wrong

Points to it
Load or tooling changed; hum with a heavier or lighter load than when tuned.
Check
Check the moment of inertia ratio setting (Yaskawa Pn103) against the real load; estimate it with the servo inertia ratio calculator and remeasure with the drive’s identification function.

3Machine resonance not filtered

Points to it
Narrow-band tone; torque ripple at a fixed frequency.
Check
Measure torque ripple (MR Configurator2 or SigmaWin+), set a notch or machine resonance suppression filter; Mitsubishi notes the resonance frequency can drift with aging.

4Mechanical looseness or backlash

Points to it
Hunting back and forth across a small band; worse with a worn coupling or belt.
Check
With power isolated, check couplings, belts, gearbox backlash and mounting bolts.

5External force on the axis (gravity, belt tension)

Points to it
Hunting only on vertical or belt-driven axes.
Check
Check counterbalance and brake, and measure position deviation while holding.

Diagnostic sequence

  1. Confirm it is the servoIf the noise stops at servo-off, it is the control loop, not the mechanics alone.
  2. Check what changedNew tooling, load, gearbox or a parameter change is the usual trigger.
  3. Check inertia ratioCompare the inertia ratio setting with the real load before touching gains.
  4. Measure the frequencyUse the drive software’s FFT or torque trace to see whether it is broadband (gain) or a single tone (resonance).
  5. Tune, then filterRerun autotuning or reduce gains; add a notch filter at the measured resonance.

Evidence to collect

Work on fuel trains, burners, pressure vessels and electrical equipment must be done by qualified personnel following the manufacturer’s documentation and local codes. Never bypass a safety device or interlock.