Mitsubishi Electric MELSERVO-J4 (MR-J4) alarm AL.50: Overload 1

Mitsubishi Electric MELSERVO-J4 (MR-J4)fault
Technical review pending. This guide is based on the cited manufacturer documentation; check it against the manual for your exact model and firmware before acting.

Alarm AL.50 on a Mitsubishi MR-J4 servo amplifier is Overload 1: the load exceeded the overload protection characteristic of the servo amplifier. Details 50.1–50.3 occur during operation, 50.4–50.6 during a stop.

Diagnose this with AI

Upload a keypad photo, the fault history or a parameter export from your Mitsubishi Electric MELSERVO-J4 (MR-J4). InduQT compares the evidence and suggests the next useful checks.

Try Free Servo Diagnostic

When it happens

Reading the subset

SubsetWhat it tells you
50.1 / 50.2 / 50.3Thermal overload error 1 / 2 / 4 during operation.
50.4 / 50.5 / 50.6Thermal overload error 1 / 2 / 4 during a stop.

Likely causes and checks

1Motor power cable disconnected or U/V/W wired wrongly

Points to it
Alarm soon after wiring work; motor turns poorly.
Check
Check the servo motor power cable and the U/V/W wiring.

2Electromagnetic brake not released

Points to it
Motor runs hot from the first move; brake click not heard.
Check
Check that the electromagnetic brake is released during operation.

3Continuous current above the amplifier rating

Points to it
High effective load ratio; alarm late in the cycle.
Check
Check the effective load ratio in MR Configurator2; reduce the load or use a larger capacity motor.

4Servo system unstable and resonating, or hunting in servo-lock

Points to it
Noise or vibration from the axis; for 50.4, hunting at standstill.
Check
Check for resonance or hunting and adjust the gains.

5Collision with the machine (during a stop)

Points to it
Detail 50.4 with the axis against an obstruction.
Check
Check whether a moving part collided with the machine.

6Wrong encoder cable destination (multi-axis) or linear encoder polarity

Points to it
Commissioning or MR-J4W unit.
Check
Check the CN2A/CN2B/CN2C connections and the linear encoder mounting polarity.

Telling it apart

Evidence to collect