Mitsubishi Electric MELSERVO-J4 (MR-J4) alarm AL.52: Error excessive

Mitsubishi Electric MELSERVO-J4 (MR-J4)fault
Technical review pending. This guide is based on the cited manufacturer documentation; check it against the manual for your exact model and firmware before acting.

Alarm AL.52 on a Mitsubishi MR-J4 servo amplifier is Error excessive: droop pulses (the difference between commanded and actual position) exceeded the alarm occurrence level. It is the MR-J4 following-error alarm.

Diagnose this with AI

Upload a keypad photo, the fault history or a parameter export from your Mitsubishi Electric MELSERVO-J4 (MR-J4). InduQT compares the evidence and suggests the next useful checks.

Try Free Servo Diagnostic

When it happens

Reading the subset

SubsetWhat it tells you
52.1 / 52.3 / 52.5Excess droop pulse 1 / 2 / 3.
52.4Error excessive during 0 torque limit: a command was given while the torque limit was 0.
52.6Excess droop pulse during servo-off: the shaft was turned by an external force.

Likely causes and checks

1Motor power or encoder cable disconnected or wired wrongly

Points to it
First move after wiring work.
Check
Check the servo motor power cable, U/V/W wiring and the encoder cable connection.

2Torque limit active, or brake not released

Points to it
Axis moves slowly or not at all before the alarm.
Check
Check whether the torque limit is in effect and whether the electromagnetic brake is released.

3Collision or insufficient torque

Points to it
Alarm at the same position or on the heaviest move; peak load ratio saturated.
Check
Check for collisions and the peak load ratio; reduce the load or review the operation pattern.

4Bus voltage dropped

Points to it
Alarm coincides with supply dips.
Check
Check the bus voltage value and the supply voltage and capacity.

5Acceleration/deceleration time constant too short, or position loop gain too small

Points to it
Alarm only on fast moves.
Check
Lengthen the time constant and check repeatability; increase the position loop gain [Pr. PB08].

6Error excessive alarm level set wrongly

Points to it
Alarm level changed from default.
Check
Check [Pr. PC24]/[Pr. PC43] on [A], or [Pr. PC01]/[Pr. PC06] on [B] [WB] [RJ010] [GF].

Telling it apart

Relevant parameters

ParameterNameWhy it matters
PB08Position loop gainMitsubishi lists a small position loop gain as a cause.
PC24, PC43 ([A]) / PC01, PC06 ([B] [WB] [RJ010] [GF])Error excessive alarm levelCheck these are set correctly for the application.

Evidence to collect

Work on fuel trains, burners, pressure vessels and electrical equipment must be done by qualified personnel following the manufacturer’s documentation and local codes. Never bypass a safety device or interlock.