ABB ACS580 fault 2310: Overcurrent

ABB ACS580faultStandard control program ASCDX 2.05
Technical review pending. This guide is based on the cited manufacturer documentation; check it against the manual for your exact model and firmware before acting.

The drive measured output current above its internal fault limit and tripped. ABB notes that the same fault can also be caused by an earth fault or by a lost supply phase, not only by a genuinely high load current.

Diagnose this with AI

Upload a keypad photo, the fault history or a parameter export from your ABB ACS580. InduQT compares the evidence and suggests the next useful checks.

Try Free Drive Diagnostic

When it happens

Likely causes and checks

1Load too heavy or acceleration too fast

Points to it
Trips during the ramp; fewer trips with a lighter load or a longer ramp.
Check
Check the motor load and the acceleration times in group 23 (speed ramp), 26 (torque) or 28 (frequency).

2Wrong scaling

Points to it
Trips after commissioning or a parameter change.
Check
Check scaling parameters 46.01, 46.02 and 46.03.

3Motor data wrong

Points to it
Drive replaced or motor changed recently.
Check
Compare the motor data in group 99 with the motor rating plate.

4Motor, cable or connection fault

Points to it
Trips instantly at start, even with little load.
Check
Check the motor and motor cable, including phasing and the star/delta connection.

5Equipment switching in the motor cable

Points to it
Trips coincide with a contactor operating between drive and motor.
Check
Check for contactors opening or closing in the motor cable while the drive runs.

6Capacitors or surge absorbers on the motor side

Points to it
Power-factor capacitors or surge absorbers are fitted in the motor cable.
Check
Check for and remove power-factor capacitors or surge absorbers from the motor cable.

7Earth fault

Points to it
Trips persist with the load removed.
Check
Measure the insulation resistance of the motor and cable, with the motor disconnected from the drive.

Telling it apart

Relevant parameters

ParameterNameWhy it matters
23.xx / 26.xx / 28.xxAcceleration times (speed, torque, frequency ramps)Too short a ramp for the load’s inertia is a common trigger.
46.01–46.03Speed, frequency and torque scalingWrong scaling is listed by ABB as a cause.
99.xxMotor dataMust match the motor rating plate.
31.12Autoreset selection (bit 0: overcurrent)Can reset overcurrent automatically; only enable once the cause is understood.

Evidence to collect

Work on fuel trains, burners, pressure vessels and electrical equipment must be done by qualified personnel following the manufacturer’s documentation and local codes. Never bypass a safety device or interlock.