ABB ACS580 fault 3210: DC link overvoltage

ABB ACS580faultStandard control program ASCDX 2.05
Technical review pending. This guide is based on the cited manufacturer documentation; check it against the manual for your exact model and firmware before acting.

The drive’s intermediate-circuit (DC link) voltage rose too high and the drive tripped. This usually happens when the motor regenerates energy while slowing down, or when the supply voltage itself is too high.

Diagnose this with AI

Upload a keypad photo, the fault history or a parameter export from your ABB ACS580. InduQT compares the evidence and suggests the next useful checks.

Try Free Drive Diagnostic

When it happens

Likely causes and checks

1Overvoltage control switched off

Points to it
Trips on stops; 30.30 is disabled.
Check
Check that 30.30 Overvoltage control is on. ABB notes it must be disabled when a brake chopper and resistor or a regenerative supply is fitted.

2Deceleration too fast

Points to it
Trips only on fast stops or large speed reductions.
Check
Check the deceleration time; use coast-to-stop where the application allows.

3Brake chopper or resistor not working, or wrongly sized

Points to it
A resistor is fitted but trips continue.
Check
Check the brake chopper and resistor, and that the resistor is dimensioned correctly with resistance within the allowed range.

4Supply voltage too high

Points to it
Trips even on gentle stops or at standstill.
Check
Check that the supply voltage matches the drive’s nominal input and look for static or transient overvoltage on the supply.

Telling it apart

Relevant parameters

ParameterNameWhy it matters
30.30Overvoltage controlReduces braking torque to hold the DC voltage down; disable when a brake chopper and resistor or a regenerative supply is used.
23.xxDeceleration timesLonger deceleration returns energy more slowly.
31.12Autoreset selection (bit 1: overvoltage)Can reset overvoltage automatically; only once the cause is understood.

Evidence to collect

Work on fuel trains, burners, pressure vessels and electrical equipment must be done by qualified personnel following the manufacturer’s documentation and local codes. Never bypass a safety device or interlock.