Fault F013 on a PowerFlex 525 is Ground Fault: the drive detected a current path to earth ground at one or more of its output terminals. Rockwell’s action is to check the motor and external wiring to the drive output terminals for a grounded condition.

Diagnose this with AI

Upload a keypad photo, the fault history or a parameter export from your Allen-Bradley (Rockwell Automation) PowerFlex 525. InduQT compares the evidence and suggests the next useful checks.

Try Free Drive Diagnostic

When it happens

Likely causes and checks

1Motor winding insulation breakdown

Points to it
Trips at start every time; motor is old, wet or has overheated.
Check
With the motor disconnected from the drive, megger each phase to ground at the motor terminals.

2Damaged motor cable or wet junction box

Points to it
Trips after washdown or rain, or when the cable moves with the machine.
Check
Megger the cable on its own (both ends disconnected) and inspect glands, conduit and junction boxes for water.

3Wiring error at the output terminals

Points to it
Trips immediately after installation or a drive swap.
Check
Check the output terminal wiring and the ground conductor routing against the manual’s wiring section.

Telling it apart

Evidence to collect

Work on fuel trains, burners, pressure vessels and electrical equipment must be done by qualified personnel following the manufacturer’s documentation and local codes. Never bypass a safety device or interlock.