Danfoss VLT AutomationDrive FC 302 fault A13: Overcurrent

Danfoss VLT AutomationDrive FC 302faultOperating Guide for software 8.43; Programming Guide for software 9.5x / 48.96
Technical review pending. This guide is based on the cited manufacturer documentation; check it against the manual for your exact model and firmware before acting.

Alarm 13 on a Danfoss VLT FC 302 is Overcurrent: output current exceeded the inverter peak current limit, approximately 200% of the drive’s rated current. Warning 13 is shown for about 1.5 s, then the drive trips and raises the alarm.

Diagnose this with AI

Upload a keypad photo, the fault history or a parameter export from your Danfoss VLT AutomationDrive FC 302. InduQT compares the evidence and suggests the next useful checks.

Try Free Drive Diagnostic

When it happens

Likely causes and checks

1Acceleration too fast for the load inertia

Points to it
Trips partway through ramp-up, more often with heavy or high-inertia loads; never at steady speed.
Check
Lengthen 3-41 Ramp 1 Ramp Up Time; Danfoss says to choose a ramp that keeps output current below 4-18 Current Limit. Compare the peak current shown on the LCP before and after.

2Shock load or jammed mechanism

Points to it
Trips at speed when the load steps, or the motor barely turns before the trip.
Check
With power removed and locked out, check that the motor shaft and driven machine turn freely (Danfoss’s first listed check).

3Motor data wrong or motor too large for the drive

Points to it
Started after a drive or motor replacement, or after a parameter reset.
Check
Check that the motor size matches the drive and that parameters 1-20 to 1-25 match the motor rating plate; run AMA (1-29) if it has not been done.

4Fast ramp-up after kinetic back-up

Points to it
Trip follows a supply dip; 14-10 Mains Failure is set to a kinetic back-up option.
Check
Read 14-10 and the alarm log times against plant supply events; Danfoss notes a quick ramp-up after kinetic back-up can cause this alarm.

5Short or ground fault in the motor or cable

Points to it
Instant trip even unloaded; may alternate with Alarm 14 or Alarm 16.
Check
Lock out, wait the discharge time on the nameplate, disconnect the motor cable at the drive, then insulation-test the cable and motor.

Telling it apart

Relevant parameters

ParameterNameWhy it matters
3-41Ramp 1 Ramp Up TimeSet so output current stays below 4-18 during the ramp.
4-18Current LimitThe limit the ramp-up time is chosen against.
1-20 to 1-25Motor dataMust match the motor rating plate.
1-29Automatic Motor Adaptation (AMA)Tunes the drive to the motor.
14-10Mains FailureKinetic back-up options can lead to A13 on a quick ramp-up afterwards.

Evidence to collect

Work on fuel trains, burners, pressure vessels and electrical equipment must be done by qualified personnel following the manufacturer’s documentation and local codes. Never bypass a safety device or interlock.