Danfoss VLT AutomationDrive FC 302 fault A7: DC Overvoltage
Alarm 7 on a Danfoss VLT FC 302 is DC Overvoltage: the DC-link voltage exceeded its limit and the drive tripped after a delay. It usually means the motor returned energy to the drive faster than the drive could absorb or dissipate it.
Diagnose this with AI
Try Free Drive Diagnostic Upload a keypad photo, the fault history or a parameter export from your Danfoss VLT AutomationDrive FC 302. InduQT compares the evidence and suggests the next useful checks.
When it happens
- During ramp-down or stopping, especially high-inertia loads
- With an overhauling load driving the motor
- During or after a supply sag
Likely causes and checks
1Ramp-down too fast for the load
- Points to it
- Trips only on stops or speed reductions; Warning 5 DC Link Voltage High may appear first.
- Check
- Lengthen 3-42 Ramp 1 Ramp Down Time or change the ramp type; Danfoss says to choose a ramp-down that avoids overvoltage from regenerative operation.
2No brake resistor, or brake function not active
- Points to it
- Process needs fast stops of a heavy load; 2-10 is Off or no resistor is fitted.
- Check
- Check 2-10 Brake Function and whether a resistor is connected; Warnings/Alarms 25–28 point to a resistor or chopper problem.
3Overvoltage control not enabled
- Points to it
- No resistor fitted and 2-17 is Disabled.
- Check
- Consider 2-17 Over-voltage Control; Danfoss says not to enable OVC in hoisting applications.
4Supply sag
- Points to it
- Trip coincides with a supply disturbance rather than a stop.
- Check
- Danfoss suggests kinetic back-up (14-10 Mains Failure) if the alarm occurs during a power sag.
Telling it apart
- Timing: on deceleration points to regenerated energy; with no stop in progress, look at the supply.
- Warning 5 DC Link Voltage High is the early warning with the drive still running; Alarm 7 is the trip.
- Danfoss also lists increasing 14-26 Trip Delay at Inverter Fault; it notes that protection mode should be disabled in hoisting applications.
Relevant parameters
| Parameter | Name | Why it matters |
|---|---|---|
| 3-42 | Ramp 1 Ramp Down Time | Longer ramp returns energy more slowly. |
| 2-10 | Brake Function | [1] Resistor brake or [2] AC brake; AC brake is less effective than a resistor. |
| 2-17 | Over-voltage Control | Reduces overvoltage trips from generative load; not for hoisting. |
| 14-26 | Trip Delay at Inverter Fault | Delay before tripping on detected overvoltage; Danfoss lists increasing it. |
| 14-10 | Mains Failure | Kinetic back-up for trips during power sags. |
Evidence to collect
- Alarm log time and whether the drive was ramping down
- DC-link voltage (16-30) trend if logged
- 3-42, 2-10, 2-17 and 14-26 settings
- Brake resistor fitted and its value
- Plant supply events at the time