Danfoss VLT AutomationDrive FC 302 fault A7: DC Overvoltage

Danfoss VLT AutomationDrive FC 302faultOperating Guide for software 8.43; Programming Guide for software 9.5x / 48.96
Technical review pending. This guide is based on the cited manufacturer documentation; check it against the manual for your exact model and firmware before acting.

Alarm 7 on a Danfoss VLT FC 302 is DC Overvoltage: the DC-link voltage exceeded its limit and the drive tripped after a delay. It usually means the motor returned energy to the drive faster than the drive could absorb or dissipate it.

Diagnose this with AI

Upload a keypad photo, the fault history or a parameter export from your Danfoss VLT AutomationDrive FC 302. InduQT compares the evidence and suggests the next useful checks.

Try Free Drive Diagnostic

When it happens

Likely causes and checks

1Ramp-down too fast for the load

Points to it
Trips only on stops or speed reductions; Warning 5 DC Link Voltage High may appear first.
Check
Lengthen 3-42 Ramp 1 Ramp Down Time or change the ramp type; Danfoss says to choose a ramp-down that avoids overvoltage from regenerative operation.

2No brake resistor, or brake function not active

Points to it
Process needs fast stops of a heavy load; 2-10 is Off or no resistor is fitted.
Check
Check 2-10 Brake Function and whether a resistor is connected; Warnings/Alarms 25–28 point to a resistor or chopper problem.

3Overvoltage control not enabled

Points to it
No resistor fitted and 2-17 is Disabled.
Check
Consider 2-17 Over-voltage Control; Danfoss says not to enable OVC in hoisting applications.

4Supply sag

Points to it
Trip coincides with a supply disturbance rather than a stop.
Check
Danfoss suggests kinetic back-up (14-10 Mains Failure) if the alarm occurs during a power sag.

Telling it apart

Relevant parameters

ParameterNameWhy it matters
3-42Ramp 1 Ramp Down TimeLonger ramp returns energy more slowly.
2-10Brake Function[1] Resistor brake or [2] AC brake; AC brake is less effective than a resistor.
2-17Over-voltage ControlReduces overvoltage trips from generative load; not for hoisting.
14-26Trip Delay at Inverter FaultDelay before tripping on detected overvoltage; Danfoss lists increasing it.
14-10Mains FailureKinetic back-up for trips during power sags.

Evidence to collect

Work on fuel trains, burners, pressure vessels and electrical equipment must be done by qualified personnel following the manufacturer’s documentation and local codes. Never bypass a safety device or interlock.