Siemens SINAMICS G120 fault F30003: DC link voltage, undervoltage
Fault F30003 on a SINAMICS G120 means the Power Module detected undervoltage in the DC link and switched off. Siemens lists a line supply failure, line voltage below the permissible value and an interrupted line phase. The undervoltage threshold depends on p0210 (unit supply voltage).
Diagnose this with AI
Try Free Drive Diagnostic Upload a keypad photo, the fault history or a parameter export from your Siemens SINAMICS G120. InduQT compares the evidence and suggests the next useful checks.
When it happens
- Running when the supply dips or fails
- During brownouts or when a phase is lost
- At power-down with an ON command still active
Likely causes and checks
1Supply failure or dip
- Points to it
- Trip matches a plant power event.
- Check
- Compare the fault time (r0948, r2130) with power-quality records.
2Line voltage below permissible value or p0210 set too high
- Points to it
- Trips under load on a weak supply; p0210 does not match the supply.
- Check
- Measure the line voltage under load and check p0210.
3Line phase interrupted
- Points to it
- Trips under load; F30011 (line phase failure) may also appear.
- Check
- With the supply isolated, check the input fuses and connections, then measure all three phases.
Telling it apart
- The converter’s automatic restart treats F30003 as a power failure: with p1210 set for restart, the drive switches the motor back on when the supply returns (the manual warns this can start the machine unexpectedly).
- F30011 is a line phase failure detected from DC link ripple or a ruptured fuse; Siemens notes it can also come from a phase failure in the motor feeder cable.
- F30027 (DC link pre-charging time monitoring) appears at power-on, not during running.
Relevant parameters
| Parameter | Name | Why it matters |
|---|---|---|
| p0210 | Unit supply voltage | Sets the undervoltage threshold; must match the supply. |
| p1210 | Automatic restart mode | Values above 1 restart the motor automatically after a power failure. |
Evidence to collect
- r0945/r0948 for F30003 and any F30011
- Measured line voltage on all phases
- p0210 setting
- Plant power events
- Automatic restart setting p1210