Siemens SINAMICS G120 fault F30001: Power unit: Overcurrent

Siemens SINAMICS G120faultCU240B-2 / CU240E-2, firmware V4.4 to V4.7
Technical review pending. This guide is based on the cited manufacturer documentation; check it against the manual for your exact model and firmware before acting.

Fault F30001 on a SINAMICS G120 means the Power Module detected an overcurrent and switched off with OFF2 (motor coasts). The fault value r0949 shows which phase tripped: bit 0 = U, bit 1 = V, bit 2 = W, bit 3 = DC link; 0 means the phase was not identified.

Diagnose this with AI

Upload a keypad photo, the fault history or a parameter export from your Siemens SINAMICS G120. InduQT compares the evidence and suggests the next useful checks.

Try Free Drive Diagnostic

When it happens

Likely causes and checks

1Short circuit or ground fault in motor or power cables

Points to it
Trips the instant the motor is switched on, even unloaded; r0949 often names one phase.
Check
Lock out, disconnect the motor cable at the converter and insulation-test motor and cable phase-to-phase and to ground.

2Motor data or connection wrong

Points to it
Trips after commissioning, a motor swap or a Power Module change.
Check
Check the motor data against the rating plate and the star/delta connection; repeat commissioning if needed.

3Ramp-up too short in U/f operation

Points to it
Trips partway through acceleration; heavier loads trip sooner.
Check
Increase p1120 (ramp-up time) and compare.

4Motor current much larger than the Power Module rating

Points to it
Motor is larger than the converter.
Check
Compare the motor rated current with the Power Module rated current.

5Line side: missing line reactor, interrupted phase, poor supply quality

Points to it
Trips on power-on or after supply dips.
Check
Check the line reactor connection, the line phases and the supply quality.

6Motor cable too long or Power Module defective

Points to it
All other checks pass.
Check
Check cable length against the Power Module limits; replace the Power Module if the fault persists.

Telling it apart

Relevant parameters

ParameterNameWhy it matters
p1120Ramp-function generator ramp-up timeFactory setting 10 s. Siemens’ remedy for U/f operation is a longer ramp.
r0949Fault valueBits 0–3 identify phase U, V, W or DC link.

Evidence to collect

Work on fuel trains, burners, pressure vessels and electrical equipment must be done by qualified personnel following the manufacturer’s documentation and local codes. Never bypass a safety device or interlock.