Siemens SINAMICS G120 fault F30005: Power unit: Overload I2t
Fault F30005 on a SINAMICS G120 means the Power Module was overloaded: its I2t value r0036 reached 100% because the permissible rated current was exceeded for too long or the load duty cycle was not maintained. Alarm A07805 warns before the trip.
Diagnose this with AI
Try Free Drive Diagnostic Upload a keypad photo, the fault history or a parameter export from your Siemens SINAMICS G120. InduQT compares the evidence and suggests the next useful checks.
When it happens
- Constant speed under sustained overload
- Repeated heavy starts (duty cycle)
- Long periods at current limit
Likely causes and checks
1Continuous load above the Power Module rating
- Points to it
- Trips after running a while; A07805 appeared first; r0036 climbs steadily.
- Check
- Trend r0036 and output current; reduce the continuous load or fit a larger Power Module.
2Duty cycle not respected
- Points to it
- Trips after several starts in quick succession.
- Check
- Compare the actual start/stop cycle with the Power Module’s permissible load duty cycle.
3Motor and Power Module current ratings mismatched
- Points to it
- Motor rated current close to or above the Power Module rating.
- Check
- Check the rated currents of motor and Power Module.
4Current limit set high
- Points to it
- p0640 well above the motor rated current.
- Check
- Reduce p0640; in U/f operation reduce p1341 (current limiting controller integral time).
Telling it apart
- F30005 is the Power Module’s thermal (time-based) overload. F30001 is an instant hardware overcurrent. F07801 is the motor current limit.
- A07805 (power unit overload I2t) is the alarm stage of the same protection: act on it before the trip.
Relevant parameters
| Parameter | Name | Why it matters |
|---|---|---|
| r0036 | Power unit overload I2t | Trips at 100%. |
| p0640 | Current limit | Siemens’ remedy includes reducing it. |
| p1341 | I_max controller integral time (U/f) | Listed in the List Manual as the I_max frequency controller integral time; reduce in U/f operation per Siemens’ remedy. |
Evidence to collect
- r0949 for F30005 (I2t, 100% = 16384)
- Trend of r0036 and output current
- Load cycle and start frequency
- p0640 and motor/Power Module ratings