ControlLogix T01:C01 after power loss, what to check first?

Question

My ControlLogix controller faulted with T01:C01 after a power bump on the machine. The RUN indicator is off and it won't restart automatically. What should I investigate first?

Top answer · Written by InduQT from the fault guide and manufacturer manuals cited below · Oct 28, 2026

A Type 1 Code 1 (T01:C01) fault on a ControlLogix controller indicates that the controller powered up in Run or Remote Run mode after a power loss. This fault prevents the controller from automatically returning to normal operation if its Power-Up Handler is not configured to clear it. The primary cause is often an external power interruption.

Likely causes and checks

1Supply interruption while in Run mode, with an unconfigured Power-Up Handler

Points to it
The controller lost power while it was in Run or Remote Run mode. When power was restored, the controller attempted to resume operation but encountered the T01:C01 fault because its Power-Up Handler routine was either empty or did not contain logic to clear this specific fault.
Check
Compare the fault timestamp with plant power records to confirm a power event. Then, open the Power-Up Handler in the program export to see if it exists and if it contains logic to clear T01:C01.

2Intentional design choice to prevent automatic restart

Points to it
The system may be deliberately configured not to restart automatically after a power loss. This is often a safety or operational decision, where a manual restart procedure is required after any power interruption.
Check
Confirm with the controls owner or relevant personnel whether automatic restart after a power loss is permitted or desired for this specific machine or process.

3Unstable controller or chassis power supply

Points to it
Fluctuations or instability in the power supply to the controller or its chassis can cause unexpected power cycles, leading to the T01:C01 fault without a clear external power outage.
Check
Measure the input voltage to the controller/chassis power supply module. Also, check the power supply module itself for any diagnostic indicators or signs of malfunction.

Next check: First, verify if the fault timestamp correlates with any known power events in the plant. If so, examine the controller's Power-Up Handler routine to see if it's designed to clear T01:C01. If not, investigate the stability of the controller's power supply.

Work on fuel trains, burners, pressure vessels and electrical equipment must be done by qualified personnel following the manufacturer’s documentation and local codes. Never bypass a safety device or interlock.