Honeywell 7800 Fault 28: Pilot Flame Failure
My industrial burner control, a Honeywell RM7800, is throwing a Fault 28. The pilot valve opens, but the pilot never lights, and the main valves never open. What should I check first?
Fault 28 indicates a pilot flame failure on a Honeywell 7800 Series relay module. This occurs during the PILOT IGN (PFEP) stage, 4 or 10 seconds after the pilot valve opens, and prevents the main valves from opening. The most common causes include issues with the pilot valve, incorrect pilot pressure, ignition problems, or detector/sighting issues.
Likely causes and checks
1Pilot pressure wrong
- Points to it
- Incorrect pilot pressure can lead to a small, lazy, or lifting pilot flame, which the system may not detect as stable. This often occurs after recent regulator adjustments.
- Check
- Measure the pilot pressure and repeat the pilot turndown test as described in the checkout publication.
2Ignition problem
- Points to it
- A lack of spark or a spark occurring in the wrong location will prevent the pilot from igniting.
- Check
- Examine the ignition transformer and the electrode for any faults or damage.
3Detector or sighting
- Points to it
- Even if a pilot flame is visible, a low flame signal indicates that the detector is not properly sensing the flame or is incorrectly sighted.
- Check
- Verify the detector sighting and check the amplifier. The minimum reliable flame signal for a pilot or main flame on the 7800 test jack is 1.25 Vdc.
Next check: If the pilot proves and the trip follows main valve opening, the fault code would be 19, not 28.
Related questions
Describe the fault or upload a photo, and InduQT checks it against the manufacturer manuals. Share the result here when it helps someone else.