Mitsubishi MR-J4 AL.16: Encoder initial comm error 1, what to check first?

Question

I'm getting an AL.16 alarm on my Mitsubishi MR-J4 servo amplifier right at power-up. This started after we replaced the motor and encoder cable. What should I check first?

Top answer · Written by InduQT from the fault guide and manufacturer manuals cited below · Oct 28, 2026

Alarm AL.16 on a Mitsubishi MR-J4 servo amplifier indicates an Encoder initial communication error 1. This means an error occurred during the initial communication between the encoder and the servo amplifier, typically at power-up or after component replacement. The detail number can provide more specific information about the failure.

Likely causes and checks

1Encoder cable disconnected, open or shorted

Points to it
This is the most common cause, especially if the alarm appears at every power-up or after the cable was recently moved or replaced.
Check
With power off, inspect the encoder cable for any disconnections, open circuits, or shorts. Repair or replace the cable as necessary.

2Wrong encoder cable communication method setting

Points to it
Incorrect settings for two-wire or four-wire communication can prevent initial communication, often indicated by detail 16.3 after commissioning or a cable change.
Check
Check the parameter setting for the encoder cable communication method: [Pr. PC22] for MR-J4-_A_ amplifiers, or [Pr. PC04] for -B, -WB, -RJ010, and -GF amplifiers.

3Unused axis not disabled (MR-J4W multi-axis)

Points to it
On multi-axis MR-J4W units, an unused axis that is not properly disabled can trigger this alarm, often with detail 16.3 on an axis without a connected motor.
Check
If using an MR-J4W multi-axis amplifier, ensure any unused axes are disabled using the disabling control axis switches (SW2-2/SW2-3/SW2-4).

4Unstable control circuit power supply

Points to it
Brief dips in the control power supply can disrupt initial communication, often accompanied by detail 16.3.
Check
Monitor the control circuit power supply voltage for any instantaneous power failures or instability.

Next check: After checking the encoder cable, verify the communication method setting in the amplifier parameters. If the issue persists, especially on a multi-axis unit, ensure all unused axes are properly disabled.