Decision engine

How InduQT makes troubleshooting decisions: rules find the event and the candidate causes, a fast AI model chooses among them, and hard-coded safety rules have the last word. Every decision is logged and learns from confirmed causes.

Engine e1Catalogue c15 equipment families

The AI is never asked “what is wrong with this machine?”. It only sees a machine once deterministic rules have found an event, and then it answers a scoped question: which of these known causes, which of these checks, how sure. Code has the final word. This keeps decisions fast, explainable and safe to show a technician.

The pipeline

  1. Rules run first.

    Every signal in the window is profiled against its own baseline: how far it moved (z-score), when it started (onset), whether it left its normal band, froze, spiked or started hunting. Signals are mapped to roles (pressure, feedwater flow, DC bus, position error…) from their names, so the same rules work on any customer’s tag names. The rules decide whether there is an event at all, classify it, set a severity floor and rank the family’s candidate causes by how well each one’s expected evidence matches.

  2. The AI gets a scoped question.

    Only if there is an event: a fast model receives a canonical state string and a fixed set of choices (event kinds, the candidate cause ids, their check ids) and must pick from them with confidences, in about a second. Anything outside the choices, below the confidence threshold, or late is discarded and the rules’ answer stands.

  3. Policy and safety have the final veto.

    A safety-critical signal out of band (low water, flame loss, overpressure) forces severity to critical and blocks “normal”. “No action needed” needs the rules and a confident AI to agree. Safety-related causes the data supports are never dropped. Checks carry their safety level (lock out / tag out, qualified personnel), and wording that suggests bypassing a protective device is removed.

  4. Everything is logged and learns.

    Each decision stores the state, the rules’ answer, the AI’s answer, the policy and any vetoes, with the engine, catalogue and state versions. When a technician confirms the actual cause, that label scores rules against AI per family, site and industry, and is the training set for a small dedicated classifier that will answer the same questions.

How it scales

What changes when you add…
AddingWhat changesCode changes
A new siteNothing: the same catalogue applies. Optional site policy (thresholds, AI on/off, notify level).None
A new industryAn industry policy with stricter or looser thresholds (pharma and chemicals require more confidence before “normal”).None
A new customer tag namingRole patterns map names like FW_FLOW or feed_water_gpm to the same role.A pattern, if a name is unusual
A new equipment familyA catalogue entry: hypotheses with their expected evidence, checks with safety levels, critical roles.Data, reviewed by an engineer
A trained modelAnswers the same questions on the same state strings; promoted per question only when it beats the current answer on confirmed outcomes.Swap the stage-2 answerer

Questions it answers

Every decision answers these, with versioned choice sets
QuestionChoicesVersion
event_kindfault, process_upset, sensor_fault, normal, insufficient_dataq1
cause_rankhypothesis ids of the machine’s family (ranked, up to 3)q1
next_checkcheck ids listed under the chosen causesq1
severityinfo, watch, act, criticalq1

Equipment families, causes and checks

The catalogue below is served live by GET /v1/decision-engine. Each cause lists the signal evidence the rules look for; each check has a safety level. This catalogue is reviewed and extended by InduQT’s engineers as confirmed outcomes come in.

Boilers & burners

Safety-critical: level down, flame down, pressure up.

Boilers & burners: candidate causes
CauseEvidence the rules look forChecks
Feedwater supply problem (pump, suction, deaerator, feed valve) (safety)
feedwater_supply
feedwater flow down; level down; pressure downCheck feedwater pump discharge pressure and amps, suction strainer, and whether a standby pump started. [Qualified personnel] · Check deaerator or feed tank level and make-up valve operation. · Test the low-water cutoffs by the manufacturer’s blowdown procedure and confirm they trip the burner. [Qualified personnel]
Steam demand above firing capacity
steam_demand_surge
steam flow up; pressure down; firing rate upCompare steam demand with the boiler’s rated output and the time of the dip. · Ask the operator what changed: load, product, setpoint, manual interventions or maintenance in the window.
Fuel supply restriction (gas pressure, regulator, strainer, valve)
fuel_supply
fuel flow down; firing rate up; pressure down; stack temp downMeasure gas pressure upstream and downstream of the regulator at high fire. [Qualified personnel] · Inspect the fuel train strainer, regulator and safety shut-off valves for restriction. [Lock out / tag out]
Combustion air problem (fan, damper linkage, intake)
combustion_air
o2 down or up; co up; valve oscillatingCheck the air damper and fuel valve linkage for slippage or play, against the commissioning settings. [Lock out / tag out] · Run a combustion analysis (O2, CO, stack temperature) at low, mid and high fire. [Qualified personnel] · Check the combustion-air proving switch and its sensing line. [Qualified personnel]
Flame detection fault (scanner, sight tube, signal) (safety)
flame_detection
flame down or spikyClean the scanner lens and sight tube, then read the flame signal at low and high fire. [Qualified personnel] · Review the controller’s alarm and event history for the window, and note the first alarm.
Fouled or scaled heat-transfer surfaces
heat_transfer_fouling
stack temp up; fuel flow upTrend net stack temperature at the same firing rate over weeks; a steady rise means fouling. · Review boiler-water TDS, hardness and blowdown records. · Schedule a fireside or waterside tube inspection at the next shutdown. [Lock out / tag out]
Control loop hunting (tuning, linkage hysteresis, valve stiction)
control_tuning
pressure oscillating; firing rate oscillating; valve oscillatingReview the pressure control loop gains and the firing-rate response to a setpoint step. · Check the air damper and fuel valve linkage for slippage or play, against the commissioning settings. [Lock out / tag out]
Sensor or transmitter fault
sensor_fault
pressure flatline or spiky; temperature flatline or spiky; flow flatline or spiky; level flatline or spikyCompare the reading with a local gauge or a second transmitter, and check its wiring, impulse line and calibration date. · Check the data path: gateway or PLC online, tag mapping, and whether the signal was frozen or substituted.
Process or demand change, not an equipment fault
process_change
steam flow up; load up; flow upAsk the operator what changed: load, product, setpoint, manual interventions or maintenance in the window. · Review the controller’s alarm and event history for the window, and note the first alarm.

Drives (VFDs)

Drives (VFDs): candidate causes
CauseEvidence the rules look forChecks
Acceleration too fast for the load
accel_overcurrent
current up; speed upCompare the acceleration time and current limit with the load inertia; trend current during start. · Review the controller’s alarm and event history for the window, and note the first alarm.
Regenerative energy on deceleration (DC bus overvoltage)
regen_overvoltage
dc bus up; speed downLengthen deceleration or check the braking resistor and chopper; confirm the bus regulator setting. · Log line voltage on all three phases at the drive input and compare with trip times. [Qualified personnel]
Supply dip or lost phase (DC bus undervoltage)
supply_sag
dc bus down; voltage downLog line voltage on all three phases at the drive input and compare with trip times. [Qualified personnel] · Check input fuses, contactor and terminal tightness on the line side. [Lock out / tag out]
Mechanical overload or binding
mechanical_load
current up; load up; speed down; vibration upWith the drive locked out, check that the driven machine turns freely and the brake releases. [Lock out / tag out] · Check the motor nameplate data and motor overload settings in the drive.
Motor or cable insulation fault
motor_insulation
current spikyInsulation-test the motor and cable with them disconnected from the drive output. [Lock out / tag out]
Drive or motor cooling problem
drive_cooling
temperature upCheck drive fans, heatsink and cabinet filters, and motor cooling. [Lock out / tag out]
Sensor or transmitter fault
sensor_fault
pressure flatline or spiky; temperature flatline or spiky; flow flatline or spiky; level flatline or spikyCompare the reading with a local gauge or a second transmitter, and check its wiring, impulse line and calibration date. · Check the data path: gateway or PLC online, tag mapping, and whether the signal was frozen or substituted.
Process or demand change, not an equipment fault
process_change
steam flow up; load up; flow upAsk the operator what changed: load, product, setpoint, manual interventions or maintenance in the window. · Review the controller’s alarm and event history for the window, and note the first alarm.

CNC machines

CNC machines: candidate causes
CauseEvidence the rules look forChecks
Cut exceeds spindle power or torque
spindle_overload
load up; current up; temperature upCompare spindle load with the program: depth of cut, feed and speed at the time of the alarm. · Inspect the tool for wear or chipping.
Axis following error: binding, lubrication or tuning
axis_following
position error up; current upWith the machine in a safe state, check the axis moves freely by hand-wheel at low speed and listen for binding. [Qualified personnel] · Check way-lube level, pump pressure and metering units. · Review servo gains and the position-deviation limit parameters against the builder’s values. [Qualified personnel]
Thermal growth affecting accuracy
thermal_drift
temperature upCompare part errors with machine warm-up time and ambient temperature. · Check coolant and spindle chiller temperatures.
Way or spindle lubrication problem
lubrication
pressure down; level downCheck way-lube level, pump pressure and metering units.
Spindle bearing wear
spindle_bearing
vibration up; temperature upMeasure spindle vibration and temperature at standard speeds and compare with baseline.
Sensor or transmitter fault
sensor_fault
pressure flatline or spiky; temperature flatline or spiky; flow flatline or spiky; level flatline or spikyCompare the reading with a local gauge or a second transmitter, and check its wiring, impulse line and calibration date. · Check the data path: gateway or PLC online, tag mapping, and whether the signal was frozen or substituted.
Process or demand change, not an equipment fault
process_change
steam flow up; load up; flow upAsk the operator what changed: load, product, setpoint, manual interventions or maintenance in the window. · Review the controller’s alarm and event history for the window, and note the first alarm.

Servo motors & drives

Servo motors & drives: candidate causes
CauseEvidence the rules look forChecks
Mechanical binding or overload on the axis
mechanical_binding
position error up; current upWith the axis in a safe state, check it moves freely through its stroke; look for crash damage, lubrication and couplings. [Qualified personnel] · Confirm the holding brake releases on servo-on (listen and measure brake voltage). [Qualified personnel]
Gains too high for the load or a mechanical resonance
tuning_resonance
position error oscillating; current oscillating; speed oscillatingRe-run auto-tuning or lower the gains, and add a notch filter at the resonance frequency. [Qualified personnel] · Calculate the load-to-motor inertia ratio and compare with the maker’s limit.
Encoder or feedback noise (cable, shield, connector)
feedback_noise
position error spiky; speed spikyInspect the encoder cable at flex points, connector pins and shield grounding; separate it from power cables. [Lock out / tag out]
Regenerative energy on deceleration
regen_overvoltage
dc bus upCheck the regenerative resistor is fitted, sized and enabled; lengthen deceleration. [Lock out / tag out]
Sustained overload (duty cycle above the motor rating)
thermal_overload
current up; temperature upCompare RMS current over the duty cycle with the motor’s continuous rating.
Sensor or transmitter fault
sensor_fault
pressure flatline or spiky; temperature flatline or spiky; flow flatline or spiky; level flatline or spikyCompare the reading with a local gauge or a second transmitter, and check its wiring, impulse line and calibration date. · Check the data path: gateway or PLC online, tag mapping, and whether the signal was frozen or substituted.
Process or demand change, not an equipment fault
process_change
steam flow up; load up; flow upAsk the operator what changed: load, product, setpoint, manual interventions or maintenance in the window. · Review the controller’s alarm and event history for the window, and note the first alarm.

Pumps, compressors, fans, chillers and conveyors

Pumps, compressors, fans, chillers and conveyors: candidate causes
CauseEvidence the rules look forChecks
Suction starvation or cavitation
cavitation_or_starvation
flow down; pressure oscillating or down; vibration up; current downCheck suction pressure, tank level, strainer and inlet valve position.
Bearing wear or misalignment
bearing_wear
vibration up; temperature upMeasure vibration and bearing temperature and compare with the baseline. · Check coupling alignment and foundation bolts at the next stop. [Lock out / tag out]
Blockage or closed valve downstream
blockage_or_restriction
pressure up; flow down; current downWalk the discharge line: valve positions, filters and check valves.
Cooling or lubrication problem
overheating
temperature up; stack temp upCheck oil level and condition, coolers and fans. [Lock out / tag out]
Leak or demand above capacity (cannot hold pressure)
leak_or_demand
pressure down; load up; current upCompare demand with capacity and run a leak survey. · Ask the operator what changed: load, product, setpoint, manual interventions or maintenance in the window.
Sensor or transmitter fault
sensor_fault
pressure flatline or spiky; temperature flatline or spiky; flow flatline or spiky; level flatline or spikyCompare the reading with a local gauge or a second transmitter, and check its wiring, impulse line and calibration date. · Check the data path: gateway or PLC online, tag mapping, and whether the signal was frozen or substituted.
Process or demand change, not an equipment fault
process_change
steam flow up; load up; flow upAsk the operator what changed: load, product, setpoint, manual interventions or maintenance in the window. · Review the controller’s alarm and event history for the window, and note the first alarm.

Policies by industry

Defaults, then the industry’s, then the site’s own overrides
IndustryMin AI confidence“Normal” needsInsight from severity
Default0.60.8act
pharma0.750.9watch
food beverage0.650.8watch
power utilities0.70.9act
chemicals0.70.9watch
manufacturing0.60.8act
buildings0.60.8act

Using it

Evaluate the last two hours of a machine
curl -X POST "https://api.induqt.ai/v1/machines/$MACHINE_ID/decisions" \
  -H "Authorization: Bearer $INDUQT_API_KEY" -H "Content-Type: application/json" -d '{}'
Confirm the cause (teaches the engine)
curl -X POST "https://api.induqt.ai/v1/decisions/$DECISION_ID/outcome" \
  -H "Authorization: Bearer $INDUQT_API_KEY" -H "Content-Type: application/json" \
  -d '{ "confirmedCause": "feedwater_supply", "checkId": "feed_pump", "note": "Suction strainer blocked" }'
How the engine is doing, by industry
curl "https://api.induqt.ai/v1/decision-engine/readout?groupBy=industry" -H "Authorization: Bearer $INDUQT_API_KEY"

Decisions also run on their own when a signal leaves its normal band, and whenever a recording is analysed. In Claude, use the evaluate_machine, record_outcome and decision_criteria tools (MCP). Full request and response shapes are in the API reference.