| Flame signal | analog Vdc, % or µA by controller | flame signal, flame strength, flame %, flame current, scanner signal, flm, flame1, flame 1, flame_signal | Flame loss while firing, Flame scanner (UV / IR), Flame rod, Flame amplifier / flame input Examples: Flame loss caused by a gas pressure sag |
| Burner sequence state | state | burner status, burner state, sequence step, sequence status, ek30, bms state, burner_status | Steam pressure drop, Controller communication network, Burner management controller Examples: Flame loss caused by a gas pressure sag |
| Combustion air proving switch | digital | air proving, airflow switch, air flow switch, air pressure switch, aps, caps, combustion air switch | Combustion airflow faults, Combustion air proving switch Examples: Fan bearing wear (FD or ID fan) |
| Combustion air pressure | analog inWC or mbar | air pressure, combustion air pressure, windbox pressure, fan pressure, fan discharge pressure | Flame loss while firing, Combustion airflow faults, Combustion air fan (FD / ID), Combustion air proving switch Examples: Fan bearing wear (FD or ID fan) |
| Combustion fan running | digital | fan run, blower run, burner motor, fan status, blower status, fan_on | Combustion air fan (FD / ID) |
| Combustion fan speed | analog % or Hz | fan speed, blower speed, vsd speed, fan vfd, fan hz | Combustion airflow faults, Combustion air fan (FD / ID) |
| Main gas pressure | analog inWC, psig or mbar | gas pressure, main gas pressure, manifold pressure, burner gas pressure, inlet gas pressure, gas_press | Flame loss while firing, Steam pressure drop, Fuel supply and regulator Examples: Flame loss caused by a gas pressure sag |
| Pilot gas pressure | analog inWC or mbar | pilot pressure, pilot gas pressure, pilot gas | Pilot gas train |
| Oil pressure | analog psig or bar | oil pressure, fuel oil pressure, atomizing pressure | Fuel supply and regulator |
| Ignition output | digital | ignition, igniter, ignition transformer, spark, ign | Ignition transformer and electrode |
| Pilot valve output | digital | pilot valve, pv, pilot solenoid | Pilot gas train |
| Main fuel valve output | digital | main valve, mv, main fuel valve, main gas valve, sov, safety shutoff valve | Main safety shutoff valves |
| Valve proof of closure | digital | proof of closure, poc, valve closed switch, pre-ignition interlock, pre ignition interlock, pii | Main safety shutoff valves |
| Running interlock / limit string | digital | running interlock, limit string, limits, run ilk, lockout interlock, safety limits | Operating and safety limits |
| Firing rate | analog % | firing rate, modulation rate, mod rate, burner load, fire rate, output % | Flame loss while firing, Combustion airflow faults, Feedwater and drum level instability, Steam pressure drop, High stack temperature, Air damper, actuator and linkage, Fuel valve actuator and linkage, Steam pressure / temperature sensor and control loop Examples: Flame loss caused by a gas pressure sag, Fouled heating surfaces (scale or soot) |
| Air damper position | analog % or ° | air damper, damper position, air servo, air actuator, air drive | Flame loss while firing, Combustion airflow faults, Air damper, actuator and linkage |
| Fuel valve position | analog % or ° | fuel valve position, gas valve position, fuel servo, fuel actuator, fuel drive, gas butterfly | Fuel valve actuator and linkage |
| Low fire position switch | digital | low fire switch, lfs, low fire proven, low fire start | Low fire and high fire position switches |
| High fire (purge) position switch | digital | high fire switch, hfs, purge position, high fire proven | Low fire and high fire position switches |
| Steam pressure | analog psig or bar | steam pressure, header pressure, drum pressure, boiler pressure, steam_press | Feedwater and drum level instability, Steam pressure drop, High stack temperature, Operating and safety limits, Steam pressure / temperature sensor and control loop, Boiler tubes and heating surfaces |
| Boiler water temperature | analog °F or °C | water temperature, supply temperature, outlet temperature, hot water temp | Operating and safety limits, Steam pressure / temperature sensor and control loop |
| Drum / water level | analog % or in | drum level, water level, gauge glass, lwco, low water cutoff | Feedwater and drum level instability, Operating and safety limits, Feedwater pump, valve and level control |
| Steam flow | analog lb/h or kg/h | steam flow, steam_flow, steam output, steam load, boiler load, steam rate | Feedwater and drum level instability, Steam pressure drop, High stack temperature, Feedwater pump, valve and level control, Boiler tubes and heating surfaces Examples: Steam temperature dip from desuperheater spray over-correction, Fouled heating surfaces (scale or soot) |
| Feedwater flow | analog lb/h, kg/h or gpm | feedwater flow, feed water flow, fw flow, feedwater | Feedwater and drum level instability, Feedwater pump, valve and level control |
| Stack (flue gas) temperature | analog °F or °C | stack temperature, stack temp, flue temperature, flue gas temperature, exhaust temperature, flue temp | Steam pressure drop, High stack temperature, Flue oxygen probe and stack sensor, Boiler tubes and heating surfaces Examples: Fouled heating surfaces (scale or soot) |
| Flue gas oxygen | analog % O2 | o2, oxygen, flue o2, excess oxygen, stack o2 | Flame loss while firing, Combustion airflow faults, High stack temperature, Flue oxygen probe and stack sensor, Boiler tubes and heating surfaces Examples: Fouled heating surfaces (scale or soot) |
| Fan vibration | analog mm/s or in/s | fan vibration, bearing vibration, vibration, fan vib, id fan vibration, fd fan vibration | Combustion air fan (FD / ID) Examples: Fan bearing wear (FD or ID fan) |
| Fan motor current | analog A | fan current, motor current, fan amps, id fan current, fd fan current, blower amps | Combustion air fan (FD / ID) Examples: Fan bearing wear (FD or ID fan) |
| Furnace temperature | analog °F or °C | furnace temperature, furnace temp, upper furnace temperature, bed temperature, furnace exit temperature | Boiler tubes and heating surfaces, Desuperheater (spray attemperator) and its control loop Examples: Steam temperature dip from desuperheater spray over-correction |
| Main steam temperature | analog °F or °C | main steam temperature, steam temperature, superheated steam temperature, sh outlet temperature, steam temp | Desuperheater (spray attemperator) and its control loop Examples: Steam temperature dip from desuperheater spray over-correction |
| Desuperheater spray valve position | analog % | spray valve, desuperheater spray valve, attemperator valve, spray valve position, desuperheater valve | Desuperheater (spray attemperator) and its control loop Examples: Steam temperature dip from desuperheater spray over-correction |
| Spray water flow | analog t/h or lb/h | spray water flow, spray flow, attemperator flow, desuperheater flow | Desuperheater (spray attemperator) and its control loop Examples: Steam temperature dip from desuperheater spray over-correction |
| Controller supply voltage | analog Vac | line voltage, supply voltage, mains, l1, 120v, 230v | Burner management controller |