Flame loss while firing: the failure signature
A flame loss while firing ends the same way every time: the flame signal drops below the control’s threshold and the burner locks out. What differs is what moved first. Looking at the minutes before the trip, in the order the signals changed, usually separates a fuel problem from an air, ratio or detection problem faster than any single alarm.
Illustrative pattern · simulated, not plant data
Diagnose this with AI
Try Free Boiler Diagnostic Upload a trend export (CSV or Excel) or a screenshot of the trend around the event. InduQT lines up which signal moved first and compares it with these variants.
Where it shows up
- Honeywell 7800 fault 17 (Main Flame Fail) or 19 (Main Flame Ign.)
- Fireye Nexus F10 with subset x15 or x16 (lost at low fire hold or modulation)
- A flame-failure alarm on the boiler HMI or DCS, often followed by low steam pressure
Signals to trend
| Signal | What it does in this failure |
|---|---|
| Flame signal | Falls to zero at the trip. A slow decline over days or weeks before the first trip points to detection; a sudden drop from a normal value means the flame really went out or the signal path broke. |
| Main gas pressure | If it sags in the seconds before the flame signal drops, the fuel supply is the lead suspect. |
| Firing rate | A trip that follows a step in firing rate points to the fuel/air curve or supply capacity at that rate. |
| Air damper position | A damper that moves without a matching fuel valve move suggests linkage slip or a servo fault. |
| Flue gas oxygen | A jump in O2 just before the trip suggests a lean flame blow-off; low O2 with CO suggests a rich, unstable flame. |
| Combustion air pressure | If air pressure falls first, follow the combustion airflow signature instead. |
Variants: what moves first, and what it points to
1Detection decay
- Points to it
- Flame signal drifts down over days or weeks; on the day of the trip, fuel, air and firing rate are steady.
- Check
- Clean the scanner sight path and confirm sighting at low and high fire; compare the flame signal with the control’s documented minimum.
2Fuel pressure sag
- Points to it
- Gas (or oil) pressure dips first, often as the burner ramps up or another user starts; the flame signal collapses within seconds.
- Check
- Trend burner fuel pressure through a ramp to high fire; check regulator response and supply capacity.
3Ratio upset at a firing-rate change
- Points to it
- Trip follows a firing-rate step; O2 swings before the flame signal falls.
- Check
- Combustion-test at the firing rate where trips happen; check linkages and servo positions against the commissioned curve.
4Signal-path noise
- Points to it
- Short drop-outs of the flame signal with no change in fuel, air or firing rate, sometimes coinciding with motor starts.
- Check
- Check scanner cable routing, screens and terminations.
How to read the trend
- Line up the tripExport flame signal, fuel pressure, firing rate, damper position and O2 for 10 minutes either side of the trip, at the fastest sample rate available.
- Find what moved firstMark the first signal to leave its normal band before the flame signal dropped.
- Check the historyCompare the flame signal at the same firing rate over the last weeks; a slow decline is a different problem from a sudden loss.
- Match to the variantUse the variants above to choose the first physical check.
Evidence to collect
- Trend export around the trip (CSV)
- Controller fault history with sequence step or subset
- Flame signal readings over recent weeks
- Recent tuning, fuel or scanner work
Work on fuel trains, burners, pressure vessels and electrical equipment must be done by qualified personnel following the manufacturer’s documentation and local codes. Never bypass a safety device or interlock.
Related
- Honeywell 7800 Series 17: Main Flame Fail
- Honeywell 7800 Series 19: Main Flame Ign.
- Fireye NX6300 (Nexus) F10: Flame Failure
- Fireye NX6100 (Nexus) F10: Flame Failure
- Components involved: Flame scanner (UV / IR), Flame amplifier / flame input, Fuel supply and regulator, Air damper, actuator and linkage, Fuel valve actuator and linkage
- Combustion airflow faults: the failure signature
- Feedwater and drum level instability: the failure signature
- Steam pressure drop: the failure signature
- High stack temperature: the failure signature