Boiler component graph

How InduQT connects fault codes, symptoms and data: each burner function is carried out by components, each component is watched through signals, and each fails in known ways. Every fault guide and failure signature points into this graph.

Limit and interlock supervision

Operating and safety limits, the running interlock string and low-water protection must be closed before and during firing.

ComponentSignalsHow it failsGuides
Operating and safety limitsRunning interlock / limit string, Steam pressure, Boiler water temperature, Drum / water levelOperating or safety limit open, Pressure or position switch out of adjustment, Welded, jumpered or miswired contactFeedwater and drum level instability, Fireye NX6300 F41, Fireye NX6100 F41
Steam pressure / temperature sensor and control loop
Also: firing-rate positioning
Steam pressure, Boiler water temperature, Firing rateTransmitter or sensor failure, Control loop tuning or strategy, Communication wiring faultSteam pressure drop, Fireye NX6300 F41, Fireye NX6100 F41
Feedwater pump, valve and level controlDrum / water level, Feedwater flow, Steam flowFeedwater supply shortfall, Control loop tuning or strategy, Transmitter or sensor failure, Operating or safety limit openFeedwater and drum level instability

Combustion air proving

The control proves combustion air is present when the fan runs, and absent when it should be off.

ComponentSignalsHow it failsGuides
Combustion air fan (FD / ID)
Also: purge
Combustion fan running, Combustion fan speed, Combustion air pressure, Fan motor current, Fan vibrationRestricted combustion air path, Fan motor or drive fault, Bearing wear or misalignmentCombustion airflow faults, Honeywell 7800 13, Honeywell 7800 23, Honeywell 7800 32, Fireye NX6300 F14, Fireye NX6300 F15, Fireye NX6300 F20, Fireye NX6100 F14, Fireye NX6100 F15, Fireye NX6100 F20, Fireye NX6100 F16
Combustion air proving switchCombustion air proving switch, Combustion air pressurePressure or position switch out of adjustment, Welded, jumpered or miswired contact, Restricted combustion air pathCombustion airflow faults, Honeywell 7800 13, Honeywell 7800 23, Honeywell 7800 32, Fireye NX6300 F14, Fireye NX6300 F15, Fireye NX6100 F14, Fireye NX6100 F15, Fireye NX6100 F16

Ignition and pilot

Spark and pilot fuel must produce a flame the detector can prove within the pilot trial time.

ComponentSignalsHow it failsGuides
Ignition transformer and electrodeIgnition outputIgniter electrode wear or wrong gap, Ignition transformer or lead failureHoneywell 7800 16, Honeywell 7800 28, Honeywell 7800 51, Fireye NX6300 F10, Fireye NX6100 F10
Pilot gas trainPilot valve output, Pilot gas pressureRegulator out of adjustment or sticking, Fuel valve not opening fully, Fuel supply pressure droopHoneywell 7800 16, Honeywell 7800 19, Honeywell 7800 28, Fireye NX6300 F10, Fireye NX6100 F10

Flame supervision

The flame detector and amplifier must see flame when it should exist and none when it should not.

ComponentSignalsHow it failsGuides
Flame scanner (UV / IR)Flame signalDirty or fogged scanner sight path, Scanner no longer sighted on the flame root, Detector or amplifier ageing, Electrical noise on signal wiringFlame loss while firing, Honeywell 7800 15, Honeywell 7800 16, Honeywell 7800 17, Honeywell 7800 19, Honeywell 7800 28, Honeywell 7800 51, Fireye NX6300 F10, Fireye NX6300 F11, Fireye NX6300 F66, Fireye NX6100 F10, Fireye NX6100 F11, Fireye NX6100 F66
Flame rodFlame signalFlame rod or burner ground fault, Scanner no longer sighted on the flame root
Flame amplifier / flame inputFlame signalWrong detector, amplifier or configuration, Detector or amplifier ageing, Electrical noise on signal wiringFlame loss while firing, Honeywell 7800 15, Honeywell 7800 16, Honeywell 7800 28, Honeywell 7800 51, Fireye NX6300 F10, Fireye NX6300 F11, Fireye NX6300 F66, Fireye NX6100 F10, Fireye NX6100 F11, Fireye NX6100 F66

Main fuel delivery

The fuel train must deliver stable pressure through the safety shutoff valves across the firing range.

ComponentSignalsHow it failsGuides
Main safety shutoff valves
Also: valve proving and proof of closure
Main fuel valve output, Valve proof of closureFuel valve not opening fully, Valve seat leakage or slow closing, Welded, jumpered or miswired contactHoneywell 7800 15, Honeywell 7800 17, Honeywell 7800 19, Honeywell 7800 33, Fireye NX6300 F11, Fireye NX6300 F42, Fireye NX6100 F11, Fireye NX6100 F42, Fireye NX6100 F30
Fuel supply and regulatorMain gas pressure, Oil pressureFuel supply pressure droop, Regulator out of adjustment or stickingFlame loss while firing, Steam pressure drop, Honeywell 7800 17, Honeywell 7800 19, Fireye NX6300 F10, Fireye NX6300 F42, Fireye NX6100 F10, Fireye NX6100 F42, Fireye NX6100 F43

Firing-rate positioning

Air damper, fuel valve and fan speed follow the commissioned fuel/air curve, proven by position switches or servo feedback.

ComponentSignalsHow it failsGuides
Air damper, actuator and linkage
Also: purge
Air damper position, Firing rateDamper or valve linkage slip, Actuator or feedback fault, Air/fuel ratio driftFlame loss while firing, Combustion airflow faults, High stack temperature, Honeywell 7800 14, Honeywell 7800 16, Honeywell 7800 17, Honeywell 7800 19, Honeywell 7800 20, Honeywell 7800 23, Honeywell 7800 32, Fireye NX6300 F10, Fireye NX6300 F14, Fireye NX6300 F20, Fireye NX6300 F64, Fireye NX6100 F10, Fireye NX6100 F14, Fireye NX6100 F20, Fireye NX6100 F64
Fuel valve actuator and linkage
Also: main fuel delivery
Fuel valve position, Firing rateDamper or valve linkage slip, Actuator or feedback fault, Air/fuel ratio driftFlame loss while firing, Steam pressure drop, Honeywell 7800 17, Honeywell 7800 20, Fireye NX6300 F20, Fireye NX6300 F64, Fireye NX6100 F20, Fireye NX6100 F64
Low fire and high fire position switches
Also: purge
Low fire position switch, High fire (purge) position switchPressure or position switch out of adjustment, Damper or valve linkage slip, Welded, jumpered or miswired contactHoneywell 7800 14, Honeywell 7800 20

Controller self-checks

The control checks its own relays, memory, inputs, supply and communications, and locks out if any check fails.

ComponentSignalsHow it failsGuides
Controller communication network
Also: firing-rate positioning
Burner sequence stateCommunication wiring fault, Electrical noise on signal wiringFireye NX6300 F20, Fireye NX6300 F41, Fireye NX6300 F66, Fireye NX6100 F20, Fireye NX6100 F41, Fireye NX6100 F66, Fireye NX6100 F43
Burner management controllerBurner sequence state, Controller supply voltageController internal fault, Supply voltage, frequency or grounding problem, Configuration or commissioning data changed, Electrical noise on signal wiringSteam pressure drop, Honeywell 7800 13, Fireye NX6300 F15, Fireye NX6300 F64, Fireye NX6100 F15, Fireye NX6100 F64

Steam temperature control

On superheated-steam boilers, desuperheater spray trims main steam temperature to its setpoint as firing and load change.

ComponentSignalsHow it failsGuides
Desuperheater (spray attemperator) and its control loopMain steam temperature, Desuperheater spray valve position, Spray water flow, Furnace temperatureControl loop tuning or strategy, Fuel valve not opening fully, Transmitter or sensor failure

Combustion monitoring

Flue oxygen, CO and stack temperature are monitored against limits, often with trim of the fuel/air ratio.

ComponentSignalsHow it failsGuides
Flue oxygen probe and stack sensorFlue gas oxygen, Stack (flue gas) temperatureTransmitter or sensor failure, Air/fuel ratio driftHigh stack temperature
Boiler tubes and heating surfacesStack (flue gas) temperature, Flue gas oxygen, Furnace temperature, Steam pressure, Steam flowFouled heating surfacesSteam pressure drop, High stack temperature

Failure mechanisms

MechanismWhat happens
Dirty or fogged scanner sight pathSoot, oil film, condensation or a dirty sight tube cuts the radiation reaching the detector, so the flame signal falls slowly over weeks.
Scanner no longer sighted on the flame rootThe scanner mount, swivel or burner geometry has moved, or the flame shape changed with tuning, so the detector sees the flame only at some firing rates.
Detector or amplifier ageingUV tubes and amplifiers lose sensitivity or fail on self-check with age; a UV tube can also fail "on" and see flame that is not there.
Flame rod or burner ground faultA cracked insulator, a rod touching metal or poor burner grounding stops the rectified flame current from flowing correctly.
Electrical noise on signal wiringIgnition or power wiring run alongside detector or low-voltage leads couples noise in, producing false flame signals or intermittent input faults.
Wrong detector, amplifier or configurationThe flame amplifier, detector type, response time or jumpers do not match each other or the application.
Igniter electrode wear or wrong gapEroded tips, carbon tracking, a cracked insulator or a gap outside the burner maker’s setting weakens or misplaces the spark.
Ignition transformer or lead failureAn open or shorted transformer winding, or a broken high-voltage lead, gives no spark or a weak one.
Fuel supply pressure droopUpstream pressure sags when the valves open or other users start, starving the flame during light-off or at high fire.
Regulator out of adjustment or stickingA pilot or main regulator delivers the wrong pressure, or responds slowly to the step in flow at light-off.
Fuel valve not opening fullyA coil, actuator or wiring fault means a safety shutoff valve opens late, partially or not at all.
Valve seat leakage or slow closingA safety shutoff valve does not seal or close in time, so a leak test, proof-of-closure or pre-ignition check fails.
Air/fuel ratio driftLinkage slip, a changed setpoint curve, fan wear or a fuel change moves the mixture away from the commissioned ratio, making the flame unstable or lifting.
Damper or valve linkage slipA loose coupling or set screw lets the damper or fuel valve move differently from the actuator that drives it.
Actuator or feedback faultA servo, feedback potentiometer or end switch no longer reports the true position, or the actuator cannot reach it.
Restricted combustion air pathA blocked intake, dirty fan wheel, closed inlet damper or flue restriction reduces the air pressure the fan can make.
Fan motor or drive faultA tripped overload, slipping belt, failed motor or a fan VSD that is slow to reach speed delays or reduces air flow.
Pressure or position switch out of adjustmentThe setpoint has drifted, the sensing tube is blocked or wet, or the contacts are dirty, so the switch makes or breaks at the wrong point.
Welded, jumpered or miswired contactA switch or relay contact stays closed when it should be open, often from a welded contact, a jumper left in place or a wiring error.
Operating or safety limit openA pressure, temperature or water-level limit opened because the process went out of range, or the limit device itself failed.
Transmitter or sensor failureA transmitter, thermocouple or probe reads out of range, drifts or loses its supply.
Communication wiring faultCANbus or fieldbus cabling, termination, addressing or screening problems interrupt messages between controller, display, servos and sensors.
Supply voltage, frequency or grounding problemLow or noisy supply voltage, wrong phasing or a missing earth upsets the controller’s safety self-checks.
Fouled heating surfacesSoot on the fire side or scale on the water side insulates the tubes, so less heat reaches the water: stack temperature and fuel use rise for the same steam output.
Control loop tuning or strategyA level, pressure or firing-rate loop is too slow, too aggressive or uses too few measurements to ride through load changes.
Feedwater supply shortfallThe feed pump, deaerator level or feedwater valve cannot deliver the flow the boiler needs at that moment.
Bearing wear or misalignmentA worn, poorly lubricated or misaligned bearing raises vibration and temperature long before the machine stops.
Controller internal faultA self-test, memory or safety-relay check inside the controller failed; the manufacturer usually directs replacement if it repeats.
Configuration or commissioning data changedJumpers, option parameters, a profile or a replaced servo no longer match what the controller stored at commissioning.

The graph is InduQT’s own engineering model, written for diagnosis rather than taken from one manufacturer. Fault codes link to guides that cite the manufacturer manual. Also in knowledge.json.