Fireye NX6100 (Nexus) fault F20: Drive position fault

Fireye NX6100 (Nexus)lockoutCommissioning Manual 1.4 (Section 5 issue 1pt4D)
Technical review pending. This guide is based on the cited manufacturer documentation; check it against the manual for your exact model and firmware before acting.

A drive position fault means a fuel or air drive (servo, or fan VSD) was not where the commissioned profile says it should be. F20 is drive 0; the following numbers are the other drives. The controller checks the close and purge positions during start-up and the fuel/air ratio while firing, so the subset tells you whether the problem is mechanical, communication or inside the servo.

Diagnose this with AI

Upload a keypad photo, the fault history or a parameter export from your Fireye NX6100 (Nexus). InduQT compares the evidence and suggests the next useful checks.

Try Free Boiler Diagnostic

When it happens

Reading the subset

SubsetWhat it tells you
000 to 016Burner status when the fault occurred (position error)
032 to 048CANbus communication error; the display shows ERR1 under the drive name
above 64Internal servo fault; the display shows ERR2 to ERR7 under the drive name

Where it sits in the burner

Supervised function: Firing-rate positioning.

ComponentSignals to look atHow it fails
Air damper, actuator and linkageAir damper position, Firing rateDamper or valve linkage slip; Actuator or feedback fault; Air/fuel ratio drift
Fuel valve actuator and linkageFuel valve position, Firing rateDamper or valve linkage slip; Actuator or feedback fault; Air/fuel ratio drift
Controller communication networkBurner sequence stateCommunication wiring fault; Electrical noise on signal wiring
Combustion air fan (FD / ID)Combustion fan running, Combustion fan speed, Combustion air pressure, Fan motor current, Fan vibrationFan motor or drive fault; Restricted combustion air path; Bearing wear or misalignment

Likely causes and checks

1Linkage or damper binding (subset 000–016)

Points to it
Fault at purge or during modulation; actuator labours or stalls.
Check
Disconnect and stroke the damper or valve by hand (burner off, qualified personnel) to check for binding; check couplings for slip.

2Stored close or purge position no longer reachable

Points to it
Fault before the drives reach purge, after mechanical work or servo replacement.
Check
The manual’s troubleshooting table points to feedback potentiometers and motor micro-switches, then resetting close and purge positions in Commission Ratio mode.

3CANbus fault (subset 032–048, ERR1)

Points to it
ERR1 under the drive name; display slow or freezing.
Check
Check CANbus wiring, screens and termination to the servo.

4Servo internal fault (subset above 64, ERR2–ERR7)

Points to it
Repeats on the same servo.
Check
Replace the servo; a replacement servo invalidates profiles that used it (F64) until re-commissioned.

5Fan VSD outside its error band

Points to it
Fault on the VSD drive while modulating; VSD current-limiting or slow ramp.
Check
Check the VSD ramp times and that its own PID is disabled, as the manual’s inverter section describes.

Telling it apart

Evidence to collect

Work on fuel trains, burners, pressure vessels and electrical equipment must be done by qualified personnel following the manufacturer’s documentation and local codes. Never bypass a safety device or interlock.