Fireye NX6100 (Nexus) fault F30: Gas Proof of Closure fault

Fireye NX6100 (Nexus)lockoutCommissioning Manual 1.4 (Section 5 issue 1pt4D)
Technical review pending. This guide is based on the cited manufacturer documentation; check it against the manual for your exact model and firmware before acting.

F30 means the proof-of-closure (POC) signal from the gas main valve 2 did not behave correctly: the controller could not confirm the valve was closed when it should be, or the signal did not change as the valve moved. The subset is the burner status at the fault.

Diagnose this with AI

Upload a keypad photo, the fault history or a parameter export from your Fireye NX6100 (Nexus). InduQT compares the evidence and suggests the next useful checks.

Try Free Boiler Diagnostic

When it happens

Reading the subset

SubsetWhat it tells you
Burner status numberWhere in the sequence the POC signal was wrong

Where it sits in the burner

Supervised function: Valve proving and proof of closure.

ComponentSignals to look atHow it fails
Main safety shutoff valvesMain fuel valve output, Valve proof of closureValve seat leakage or slow closing; Fuel valve not opening fully; Welded, jumpered or miswired contact

Likely causes and checks

1Valve not closing fully or slowly

Points to it
Fault at shutdown or just before start.
Check
Have the valve actuator and seat inspected; time the closing stroke.

2POC switch adjustment or wiring

Points to it
Valve closes but the signal does not change.
Check
Check the POC switch and its wiring to the controller input.

Telling it apart

Evidence to collect

Work on fuel trains, burners, pressure vessels and electrical equipment must be done by qualified personnel following the manufacturer’s documentation and local codes. Never bypass a safety device or interlock.