Fireye NX6300 (Nexus) fault F64: Profile Invalid

Fireye NX6300 (Nexus)lockoutFirmware 1.4
Technical review pending. This guide is based on the cited manufacturer documentation; check it against the manual for your exact model and firmware before acting.

F64 means the controller will not fire the selected fuel/air profile because its data no longer matches the burner configuration. This is a deliberate safety block: a drive was deselected, a servo was replaced, or the profile was uploaded from a PC and not yet verified on this burner.

Diagnose this with AI

Upload a keypad photo, the fault history or a parameter export from your Fireye NX6300 (Nexus). InduQT compares the evidence and suggests the next useful checks.

Try Free Boiler Diagnostic

When it happens

Reading the subset

SubsetWhat it tells you
Drive numberA drive used in the profile has since been deselected
Profile + 100The profile uses a servo that was replaced, or was uploaded and not verified

Where it sits in the burner

Supervised functions: Firing-rate positioning, Controller self-checks.

ComponentSignals to look atHow it fails
Burner management controllerBurner sequence state, Controller supply voltageConfiguration or commissioning data changed; Controller internal fault; Supply voltage, frequency or grounding problem; Electrical noise on signal wiring
Fuel valve actuator and linkageFuel valve position, Firing rateDamper or valve linkage slip; Actuator or feedback fault; Air/fuel ratio drift
Air damper, actuator and linkageAir damper position, Firing rateDamper or valve linkage slip; Actuator or feedback fault; Air/fuel ratio drift

Likely causes and checks

1Servo replaced

Points to it
After a servo swap; subset is the profile number plus 100.
Check
A qualified commissioning engineer checks the new servo is mounted the same way and re-commissions the profile, acknowledging every point up to high fire.

2Drive deselected

Points to it
After option parameter changes; subset is a drive number.
Check
Restore the drive selection or re-commission the profile without it.

3Profile uploaded but not verified

Points to it
After restoring settings from ComFire2 or a PC.
Check
Verify the profile on the burner in Commission Ratio mode.

Telling it apart

Evidence to collect

Work on fuel trains, burners, pressure vessels and electrical equipment must be done by qualified personnel following the manufacturer’s documentation and local codes. Never bypass a safety device or interlock.