Fireye NX6100 (Nexus) fault F66: Flame Test

Fireye NX6100 (Nexus)lockoutCommissioning Manual 1.4 (Section 5 issue 1pt4D)
Technical review pending. This guide is based on the cited manufacturer documentation; check it against the manual for your exact model and firmware before acting.

The controller regularly checks that its flame input reads "no flame" when it should, using the scanner shutter or the detector’s own self-check. F66 means that test failed, so the controller can no longer trust the flame input. Left alone, a failing UV tube can show flame that is not there.

Diagnose this with AI

Upload a keypad photo, the fault history or a parameter export from your Fireye NX6100 (Nexus). InduQT compares the evidence and suggests the next useful checks.

Try Free Boiler Diagnostic

When it happens

Reading the subset

SubsetWhat it tells you
1Shutter not detected (shuttered UV)
2Flame input circuit failure
3Input stuck on, or terminals short-circuited
1xx / 2xxSelf-check detector on flame 1 or flame 2 (when the scanner option is set for it), followed by the codes below
+1CANbus time-out: check wiring
+2 to +4Detector memory fault: replace the detector
+5, +6Detector internal fault: replace the detector
+7Shutter or dark check failed, or UV tube failed: check the detector out of the burner

Where it sits in the burner

Supervised functions: Flame supervision, Controller self-checks.

ComponentSignals to look atHow it fails
Flame scanner (UV / IR)Flame signalDetector or amplifier ageing; Electrical noise on signal wiring; Dirty or fogged scanner sight path; Scanner no longer sighted on the flame root
Flame amplifier / flame inputFlame signalDetector or amplifier ageing; Electrical noise on signal wiring; Wrong detector, amplifier or configuration
Controller communication networkBurner sequence stateCommunication wiring fault; Electrical noise on signal wiring

Likely causes and checks

1UV tube failing or shutter stuck

Points to it
Subset 1 or +7; may be preceded by F11 events.
Check
Test the scanner outside the burner as the manual directs; replace if the dark check still fails.

2Flame input wiring short

Points to it
Subset 3; after wiring work or cable damage.
Check
Check the scanner cable and terminals for shorts.

3Self-check detector fault

Points to it
Subsets x02–x06.
Check
The manual directs replacing the detector for memory or internal faults.

4CANbus to the detector

Points to it
Subset x01.
Check
Check CANbus wiring to the detector.

Telling it apart

Evidence to collect

Work on fuel trains, burners, pressure vessels and electrical equipment must be done by qualified personnel following the manufacturer’s documentation and local codes. Never bypass a safety device or interlock.