Combustion airflow faults: the failure signature
The burner control proves combustion air with a pressure switch or sensor. An airflow trip means that proof dropped out, or appeared when it should not. The useful question is whether the air really fell, or the switch saw it wrong: trending air pressure, fan speed and damper position next to the switch state answers it.
Illustrative pattern · simulated, not plant data
Diagnose this with AI
Try Free Boiler Diagnostic Upload a trend export (CSV or Excel) or a screenshot of the trend around the event. InduQT lines up which signal moved first and compares it with these variants.
Where it shows up
- Honeywell 7800 faults 23 and 32 (Airflow Switch) or 13 (Airflow Sw. On)
- Fireye Nexus F14 (air pressure not detected) or F15 (detected when it should not be); NX6100 F16 for a second air switch
- Repeated purge failures or trips on modulating down to low fire
Signals to trend
| Signal | What it does in this failure |
|---|---|
| Combustion air proving switch | Drops to 0 at the trip. Chatter (rapid 1/0) with steady air pressure points to the switch or its sensing line. |
| Combustion air pressure | Falls toward the switch setpoint before a genuine loss. A small margin at low fire is the most common cause of intermittent trips. |
| Combustion fan speed | A drop in speed or a VSD current limit just before the trip points to the fan drive. |
| Air damper position | Trips that only happen near minimum damper position suggest the switch margin at low fire. |
| Flue gas oxygen | Falls as air is lost; steady O2 during a trip suggests the air did not actually fall. |
| Firing rate | Shows where in the firing range the trip happened. |
Variants: what moves first, and what it points to
1Low switch margin at low fire
- Points to it
- Trips when the burner modulates down; air pressure at low fire sits just above the switch setpoint.
- Check
- Measure the differential at the switch across the firing range and compare with its setpoint and the burner maker’s settings.
2Restricted air path
- Points to it
- Air pressure at the same damper position falls slowly over weeks; O2 at low fire trends down.
- Check
- Inspect the intake, fan wheel, inlet damper and flue for restrictions.
3Fan drive problem
- Points to it
- Fan speed or current changes just before the trip; VSD fault or current-limit events.
- Check
- Check the fan VSD fault log, ramp settings, belts and motor.
4Switch or sensing line fault
- Points to it
- Proving signal chatters while air pressure is steady; water in the sensing tube.
- Check
- Clear and re-route the sensing tube; check switch contacts and wiring.
5Air proven with the fan off
- Points to it
- Proving signal is 1 in standby or minutes after shutdown.
- Check
- Check for a welded contact or jumper, a fan that keeps running, or stack draft through the boiler.
How to read the trend
- Read the state of the switchWas air lost when it was needed, or seen when it should not be? The fault code or subset says which.
- Plot the marginTrend air pressure (or the differential at the switch) against firing rate. Note the lowest value during normal running.
- Check the fanLook at fan speed, current and VSD events in the same window.
- Compare O2If O2 did not move at the trip, the air probably did not fall: look at the switch and its tubing.
Evidence to collect
- Fault code or subset
- Air pressure or switch differential across the firing range
- Fan VSD status and fault log
- Flue O2 trend
Work on fuel trains, burners, pressure vessels and electrical equipment must be done by qualified personnel following the manufacturer’s documentation and local codes. Never bypass a safety device or interlock.
Related
- Honeywell 7800 Series 23: Airflow Switch
- Honeywell 7800 Series 32: Airflow Switch
- Honeywell 7800 Series 13: Airflow Sw. On
- Fireye NX6300 (Nexus) F14: Combustion air pressure not detected
- Fireye NX6300 (Nexus) F15: Combustion air pressure detected when it should not be
- Fireye NX6100 (Nexus) F16: Second (primary) air pressure not detected
- Components involved: Combustion air proving switch, Combustion air fan (FD / ID), Air damper, actuator and linkage
- Flame loss while firing: the failure signature
- Feedwater and drum level instability: the failure signature
- Steam pressure drop: the failure signature
- High stack temperature: the failure signature