Rockwell Automation / Allen-Bradley ControlLogix / CompactLogix (Logix 5000) fault T04:C83: Program fault: value out of range

Rockwell Automation / Allen-Bradley ControlLogix / CompactLogix (Logix 5000)faultFault code list 1756-RD001F (September 2025)

The data tested was not inside the required limits. Rockwell notes that this occurs with array subscripts used with Boolean arrays and bit-level addressing. Corrective action: adjust the value to be within the valid range and do not exceed the array size or its defined dimensions.

Diagnose this with AI

Upload a keypad photo, the fault history or a parameter export from your Rockwell Automation / Allen-Bradley ControlLogix / CompactLogix (Logix 5000). InduQT compares the evidence and suggests the next useful checks.

Try Free PLC Fault Diagnostic

When it happens

Likely causes and checks

1Bit index or Boolean array subscript beyond the array size

Points to it
Fault in logic like BoolArray[Index] or Word.[Bit] with an indirect bit number.
Check
Read the index value at the fault and compare it with the BOOL array length or the bits in the data type.

2Index calculated or entered without range checking

Points to it
Fault follows a calculation, HMI or recipe change to the index.
Check
Limit-check the index where it is written.

Telling it apart

Evidence to collect

Work on fuel trains, burners, pressure vessels and electrical equipment must be done by qualified personnel following the manufacturer’s documentation and local codes. Never bypass a safety device or interlock.