Servo overload alarm
A servo overload alarm means the drive’s thermal model of the motor or amplifier says it has been working too hard. Short, very high overloads usually come from a jam, collision, dragging brake or wiring fault; slow, continuous overloads come from the duty cycle, friction or holding a load at standstill. When it trips, and whether a warning came first, tells you which.
Diagnose this with AI
Try Free Servo Diagnostic Upload a photo of the alarm screen, the fault history or a data export. InduQT compares the evidence and suggests the next useful checks.
Where it shows up
- Yaskawa Σ-7: A.710 Instantaneous Overload, A.720 Continuous Overload (warning A.910 first)
- Mitsubishi MR-J4: AL.50 Overload 1, AL.51 Overload 2 (warning AL.E1 first)
- Mitsubishi MR-J5: AL.050 Overload 1, AL.051 Overload 2 (warning AL.0E1)
- Allen-Bradley Kinetix 5700: FLT S07/S08 MTR OVERLOAD, FLT S13/S14 INV OVERLOAD
- FANUC αi with CNC: 436 Soft thermal (OVC)
Likely causes and how to tell them apart
1Brake not released or mechanism jammed
- Points to it
- Trips quickly from the first move; motor speed does not follow the command.
- Check
- Confirm the holding brake releases, then turn the mechanism by hand with power isolated.
2Motor power wiring wrong or open phase
- Points to it
- Trips right after wiring work; motor growls.
- Check
- Check U/V/W phase order and connections at drive and motor.
3Collision or torque saturation
- Points to it
- Short-time overload (A.710, AL.51) at the same position each time.
- Check
- Check for collisions and the peak torque against the motor limit.
4Duty cycle too demanding
- Points to it
- Continuous overload (A.720, AL.50, S07) after running a while; warnings before the alarm.
- Check
- Compare effective (RMS) torque over the cycle with the motor continuous rating; lengthen accel/decel or reduce speed.
5Rising friction or holding load
- Points to it
- Torque at constant speed or at standstill has crept up.
- Check
- Trend torque over weeks; check lubrication, alignment, bearings and counterbalance.
6Resonance or hunting
- Points to it
- Overload while stopped with audible hum (MR-J4 AL.50.4).
- Check
- Check for hunting in servo-lock and retune.
Diagnostic sequence
- Read the code and detailInstantaneous vs continuous, running vs stopped (MR-J4 50.1 vs 50.4) narrows the search immediately.
- Look for warnings firstAn overload warning before the alarm means heat built up over time; no warning points to a sudden jam.
- Check brake and wiringRule out a dragging brake or a wiring fault before changing the profile.
- Measure torqueTrend torque over a full cycle and compare RMS torque with the motor rating.
- Let it coolMitsubishi asks for about 30 minutes of cooling after an overload alarm; do not reset repeatedly.
Evidence to collect
- Exact alarm code with detail number
- Alarm and warning history with times
- Torque trend over a full cycle
- Brake release confirmation
- Recent changes to speed, load or mechanics
Work on fuel trains, burners, pressure vessels and electrical equipment must be done by qualified personnel following the manufacturer’s documentation and local codes. Never bypass a safety device or interlock.