Yaskawa Σ-7 (Sigma-7) SERVOPACK alarm A.100: Overcurrent Detected

Yaskawa Σ-7 (Sigma-7) SERVOPACKfault
Technical review pending. This guide is based on the cited manufacturer documentation; check it against the manual for your exact model and firmware before acting.

Alarm A.100 on a Yaskawa Σ-7 SERVOPACK is Overcurrent Detected: an overcurrent flowed through the power transistor or the heat sink overheated. It is a Gr.1 alarm and cannot be cleared with an alarm reset.

Diagnose this with AI

Upload a keypad photo, the fault history or a parameter export from your Yaskawa Σ-7 (Sigma-7) SERVOPACK. InduQT compares the evidence and suggests the next useful checks.

Try Free Servo Diagnostic

When it happens

Likely causes and checks

1Main circuit cable miswired, loose, short-circuited or ground-faulted

Points to it
Trips the instant servo turns ON, even unloaded.
Check
With power isolated and the bus discharged, check the wiring, then check for shorts between U, V, W and between each phase and ground on the cable.

2Short circuit or ground fault inside the Servomotor

Points to it
Cable tests good; coolant ingress at the motor.
Check
Test U, V, W phase-to-phase and phase-to-ground at the motor with it disconnected from the SERVOPACK; replace the motor if faulty.

3Short circuit or ground fault inside the SERVOPACK

Points to it
Alarm with the motor disconnected.
Check
Check for shorts across the SERVOPACK U, V, W terminals and to ground; replace the SERVOPACK if faulty.

4Regenerative resistor wiring, capacity or resistance problem

Points to it
Trips on deceleration of large loads.
Check
Check the regenerative resistor wiring and the regenerative load ratio in SigmaWin+; use a resistance not below the SERVOPACK minimum allowable value.

5Frequent dynamic brake stops (A.730/A.731 history)

Points to it
Repeated emergency stops with the dynamic brake.
Check
Check how often the DB is used and whether A.730 or A.731 occurred.

6Heavy load at standstill or low speed, or noise

Points to it
Trips while holding or crawling; or random trips with poor FG wiring.
Check
Compare the operating conditions with the specifications; improve FG wiring (FG wire size equal to the main circuit wire size).

Telling it apart

Evidence to collect

Work on fuel trains, burners, pressure vessels and electrical equipment must be done by qualified personnel following the manufacturer’s documentation and local codes. Never bypass a safety device or interlock.