Yaskawa Σ-7 (Sigma-7) SERVOPACK alarm A.C90: Encoder Communications Error
Alarm A.C90 on a Yaskawa Σ-7 SERVOPACK is Encoder Communications Error: communications between the encoder and the SERVOPACK are not possible. It is a Gr.1 alarm and cannot be cleared with an alarm reset until the cause is removed.
Diagnose this with AI
Try Free Servo Diagnostic Upload a keypad photo, the fault history or a parameter export from your Yaskawa Σ-7 (Sigma-7) SERVOPACK. InduQT compares the evidence and suggests the next useful checks.
When it happens
- At power-up, when the SERVOPACK first tries to talk to the encoder (connector, wiring or encoder fault)
- During operation or motion, when vibration or cable flexing breaks contact, or noise corrupts the data
- After the motor, cable or SERVOPACK was replaced or reconnected
Likely causes and checks
1Faulty contact or wrong wiring at the encoder connector
- Points to it
- Alarm at power-up, often right after a motor or cable change.
- Check
- Check the condition of the encoder connector at both ends, reconnect it and check the encoder wiring.
2Encoder Cable open, shorted, or outside the specified impedance
- Points to it
- Alarm repeats at power-up or comes and goes with cable movement (cable carrier, robot dress pack).
- Check
- With power off, check the Encoder Cable for continuity and shorts and confirm it is a cable within Yaskawa’s specifications (shielded twisted pair, 50 m maximum for rotary motors).
3Environmental damage: corrosion, water or cutting oil in the connector, or contact loosened by vibration
- Points to it
- Machine tool or washdown area; green or wet pins; alarm appears during machining vibration.
- Check
- Inspect the connectors and operating environment; improve the environment and replace the cable. If the alarm continues, Yaskawa says to replace the SERVOPACK.
4Noise on the encoder signal
- Points to it
- Random alarms, more frequent when other large loads switch; encoder cable run beside the motor power cable.
- Check
- Separate the Encoder Cable from the Servomotor Main Circuit Cable and ground the encoder correctly, then see if the alarm stops.
5SERVOPACK or encoder (motor) failure
- Points to it
- Wiring and environment are good and the alarm is persistent.
- Check
- Swap test: connect the Servomotor to another SERVOPACK and turn on control power. No alarm means the SERVOPACK is faulty; alarm follows the motor means the motor encoder is faulty.
6Reserved parameter Pn0D8 changed from its default
- Points to it
- Parameters were copied from another machine or edited.
- Check
- Initialize the parameter settings (after saving a backup) as Yaskawa directs.
Telling it apart
- A.C90 means no communication at all; A.C91 is a position data acceleration-rate error (noise or bent cable while running) and A.C92 is a communications timer error. A.C91/A.C92 point more toward noise, vibration and shock than toward an open conductor.
- If the alarm only appears with the axis moving, suspect the cable in the carrier or a vibrating connector; if it appears every time at power-up, suspect a connector, an open conductor or the encoder itself.
- The swap test with another SERVOPACK is the quickest way to decide whether the drive or the motor goes for repair.
Relevant parameters
| Parameter | Name | Why it matters |
|---|---|---|
| Pn0D8 | Reserved parameter | Yaskawa lists a non-default value here as a cause of A.C90; initialize parameters to correct it. |
Evidence to collect
- Alarm history showing when A.C90 occurred and whether A.C91/A.C92 also appear
- Encoder Cable part number and length
- Photos of both connectors
- Result of the swap test with another SERVOPACK
- Whether the cable runs in a carrier or alongside the motor power cable