Yaskawa Σ-7 (Sigma-7) SERVOPACK alarm A.d00: Position Deviation Overflow

Yaskawa Σ-7 (Sigma-7) SERVOPACKfault
Technical review pending. This guide is based on the cited manufacturer documentation; check it against the manual for your exact model and firmware before acting.

Alarm A.d00 on a Yaskawa Σ-7 SERVOPACK is Position Deviation Overflow: the position deviation (following error) exceeded the setting of Pn520 (Position Deviation Overflow Alarm Level). It is the Σ-7 equivalent of a following-error fault.

Diagnose this with AI

Upload a keypad photo, the fault history or a parameter export from your Yaskawa Σ-7 (Sigma-7) SERVOPACK. InduQT compares the evidence and suggests the next useful checks.

Try Free Servo Diagnostic

When it happens

Likely causes and checks

1Servomotor U, V, W wiring incorrect or loose

Points to it
Fault on the first move after a rewire; motor jerks or runs away briefly.
Check
Check the wiring of the Servomotor Main Circuit Cables and the encoder for faulty contacts.

2Position reference speed too fast

Points to it
Fault only at the highest speeds.
Check
Reduce the reference speed and try again; reconsider the electronic gear ratio.

3Position reference acceleration too high

Points to it
Fault during the acceleration ramp, not at constant speed.
Check
Reduce the reference acceleration, or smooth it with the position reference filter (ACCFIL) in the MECHATROLINK command.

4Pn520 set too low for the operating conditions

Points to it
Motion is healthy but deviation at top speed is close to Pn520.
Check
Compare Pn520 with Yaskawa’s formula: maximum speed/60 × encoder resolution/(Pn102/10) × Pn210/Pn20E × (1.2 to 2).

5SERVOPACK failure

Points to it
Wiring, reference and settings all check good.
Check
Cycle power; if the alarm persists, Yaskawa says the SERVOPACK may be faulty.

Telling it apart

Relevant parameters

ParameterNameWhy it matters
Pn520Position Deviation Overflow Alarm LevelRange 1 to 1,073,741,823 reference units; default 5,242,880.
Pn51EPosition Deviation Overflow Warning Level10 to 100 %, default 100 %; A.900 occurs at Pn520 × Pn51E/100.
Pn102Position Loop GainUsed in the Pn520 sizing formula (Pn141 instead when model following control is enabled).
Pn526Position Deviation Overflow Alarm Level at Servo ONThreshold for A.d01.

Evidence to collect

Work on fuel trains, burners, pressure vessels and electrical equipment must be done by qualified personnel following the manufacturer’s documentation and local codes. Never bypass a safety device or interlock.