Yaskawa Σ-7 (Sigma-7) SERVOPACK alarm A.810: Encoder Backup Alarm
Alarm A.810 on a Yaskawa Σ-7 SERVOPACK is Encoder Backup Alarm: the power supplies to the absolute encoder all failed and the position data was lost. It cannot be reset; the encoder must be set up again (and the machine re-referenced) after the cause is fixed.
Diagnose this with AI
Try Free Servo Diagnostic Upload a keypad photo, the fault history or a parameter export from your Yaskawa Σ-7 (Sigma-7) SERVOPACK. InduQT compares the evidence and suggests the next useful checks.
When it happens
- At power-up, the first time an absolute encoder is powered
- At power-up after the Encoder Cable was disconnected, or the battery removed, while control power was off
- At power-up after a long shutdown with a flat battery
Likely causes and checks
1First power-up of the absolute encoder
- Points to it
- New motor or new machine.
- Check
- Confirm it is the first power-up and set up (reset) the absolute encoder with Fn008.
2Encoder Cable disconnected and reconnected
- Points to it
- Motor or cable was changed, or the connector was opened during maintenance.
- Check
- Check the encoder connection and set up the encoder.
3No power from either the SERVOPACK (+5 V) or the battery
- Points to it
- Battery old or missing; A.830 or A.930 seen before.
- Check
- Check the battery and the connector status; replace the battery with control power ON, then set up the encoder.
4Absolute encoder failure
- Points to it
- Alarm returns after a correct setup with a good battery.
- Check
- Set up the encoder again; if the alarm still occurs, replace the Servomotor.
5SERVOPACK failure
- Points to it
- Encoder and battery check good.
- Check
- Yaskawa’s listed action is to replace the SERVOPACK.
Telling it apart
- A.830 (Encoder Battery Alarm) and warning A.930 mean the battery voltage is low (about 2.7 V or less) but the position is still held; A.810 means the backup was lost and position data is gone.
- Yaskawa warns that removing the battery or disconnecting the Encoder Cable while SERVOPACK control power is OFF loses the absolute data. Change batteries with only control power ON.
- After an A.810 the machine position must be re-established; do not run automatic cycles until the axis is referenced again.
Relevant parameters
| Parameter | Name | Why it matters |
|---|---|---|
| Pn008 | Low Battery Voltage Alarm/Warning Selection | n.□□□0 (default) gives alarm A.830 at power-up; n.□□□1 gives warning A.930 and monitors continuously. |
Evidence to collect
- Alarm history showing A.810 and any earlier A.830/A.930
- Battery voltage measured with a meter
- What maintenance was done while power was off
- Battery location (host controller or encoder cable battery case)
Work on fuel trains, burners, pressure vessels and electrical equipment must be done by qualified personnel following the manufacturer’s documentation and local codes. Never bypass a safety device or interlock.