Yaskawa Σ-7 (Sigma-7) SERVOPACK alarm A.400: Overvoltage

Yaskawa Σ-7 (Sigma-7) SERVOPACKfault
Technical review pending. This guide is based on the cited manufacturer documentation; check it against the manual for your exact model and firmware before acting.

Alarm A.400 on a Yaskawa Σ-7 SERVOPACK is Overvoltage: the main circuit DC voltage is too high. It is detected in the main circuit power supply section and can be reset once the cause is removed.

Diagnose this with AI

Upload a keypad photo, the fault history or a parameter export from your Yaskawa Σ-7 (Sigma-7) SERVOPACK. InduQT compares the evidence and suggests the next useful checks.

Try Free Servo Diagnostic

When it happens

Likely causes and checks

1Supply voltage above the specified range, or unstable/surge

Points to it
Trips even with no motion; other equipment on the same supply sees surges.
Check
Measure the power supply voltage; set it within range and fit a surge absorber where needed.

2External regenerative resistance too high for the operating conditions

Points to it
Trips on deceleration; resistor value larger than needed.
Check
Check the operating conditions against the regenerative resistance and select a suitable value.

3Moment of inertia ratio or mass ratio above the allowable value

Points to it
Trips on fast stops of a heavy load.
Check
Check that the moment of inertia ratio is within the allowable range; increase the deceleration time or reduce the load.

4Regenerative resistor disconnected while the supply voltage was high

Points to it
Resistor open-circuit when measured.
Check
Measure the regenerative resistor; replace the external resistor, or the SERVOPACK if the built-in one has failed.

5SERVOPACK failure

Points to it
Alarm persists after cycling control power with the main circuit OFF.
Check
Yaskawa’s listed action is to replace the SERVOPACK.

Telling it apart

Relevant parameters

ParameterNameWhy it matters
Pn600Regenerative Resistor CapacityMust match the external regenerative resistor fitted.

Evidence to collect

Work on fuel trains, burners, pressure vessels and electrical equipment must be done by qualified personnel following the manufacturer’s documentation and local codes. Never bypass a safety device or interlock.