VFD DC bus undervoltage trip
A drive trips on DC bus undervoltage when the voltage on its internal DC link falls below a limit. Usually the supply sagged or lost a phase, or an input connection is loose. Less often the cause is inside the drive (precharge circuit or worn DC bus capacitors), or the ride-through settings do not suit the plant supply.
Diagnose this with AI
Try Free Drive Diagnostic Upload a photo of the alarm screen, the fault history or a data export. InduQT compares the evidence and suggests the next useful checks.
Where it shows up
- Danfoss FC 302 Alarm 8 DC Undervoltage, often with Alarm 4 Mains Phase Loss or Alarm 36 Mains Failure
- Schneider ATV320 USF Supply mains undervoltage, often with PHF Input phase loss
- Undervoltage faults on other drives during plant supply events
Likely causes and how to tell them apart
1Supply sags and dips
- Points to it
- Trips coincide with large motors starting, utility events or storms; other equipment reacts too.
- Check
- Compare trip times with power-quality records; measure supply voltage at the drive under load.
2Lost phase or blown fuse
- Points to it
- Phase-loss code logged as well; one phase low or missing.
- Check
- Measure all three input phases at the drive and check fuses with the supply locked out.
3Loose or burnt input terminals or contactor contacts
- Points to it
- Intermittent trips under load; discoloured terminal or contactor pole.
- Check
- Lock out, inspect and re-torque input terminals; check contactor contacts.
4Precharge (soft-charge) circuit fault
- Points to it
- Supply is healthy but trips repeat, or the drive faults at power-up (Schneider CRF1, Danfoss soft-charge test).
- Check
- Follow the manual’s soft-charge or precharge check; refer to qualified service.
5Aging DC bus capacitors
- Points to it
- Old drive; trips on load steps that it used to ride through, with a healthy supply.
- Check
- Have the drive assessed by the manufacturer’s service; capacitor work is inside the power section.
6Ride-through settings not suited to the supply
- Points to it
- Short dips cause trips that the process could tolerate.
- Check
- Review Danfoss 14-10/14-11 or ATV320 USB, UST and STP against the plant supply and the process.
Diagnostic sequence
- Read the code and logNote the time and any phase-loss or mains-failure codes logged with it; on the ATV320 the error record stores mains voltage.
- Match to supply eventsIf other loads tripped or flickered at the same time, the supply is the first suspect.
- Measure under loadMeasure all three phases at the drive input while it runs loaded.
- Check connectionsWith the supply locked out, check fuses, input terminals and contactor contacts.
- Then the driveIf the supply and connections are good, follow the manual’s precharge checks and refer internal faults to service.
- Tune ride-through lastAdjust the mains-failure or undervoltage handling only once the supply is understood, and confirm the process can tolerate the chosen behaviour.
Evidence to collect
- Fault code and log entries with times
- Supply voltage per phase at the drive under load
- Power-quality records
- Fuse, terminal and contactor condition
- Mains-failure / undervoltage handling settings
- Drive age
Work on fuel trains, burners, pressure vessels and electrical equipment must be done by qualified personnel following the manufacturer’s documentation and local codes. Never bypass a safety device or interlock.