Siemens SINAMICS G120 warning A07910: Motor overtemperature

Siemens SINAMICS G120warningCU240B-2 / CU240E-2, firmware V4.4 to V4.7
Technical review pending. This guide is based on the cited manufacturer documentation; check it against the manual for your exact model and firmware before acting.

Alarm A07910 on a SINAMICS G120 means the measured motor temperature (KTY sensor) or the motor thermal model exceeded the alarm threshold p0604, or a PTC or bimetal contact responded. It is an alarm, not a fault: the drive keeps running, and p0610 decides whether current is reduced and whether fault F07011 follows.

Diagnose this with AI

Upload a keypad photo, the fault history or a parameter export from your Siemens SINAMICS G120. InduQT compares the evidence and suggests the next useful checks.

Try Free Drive Diagnostic

When it happens

Likely causes and checks

1Motor overloaded

Points to it
Alarm after sustained high current.
Check
Check the motor load and current against the rating plate.

2Motor cooling impaired or ambient too hot

Points to it
Fan cover blocked or dirty; hot area.
Check
Check the motor’s ambient temperature and cooling air path.

3Temperature sensor or wiring problem

Points to it
Alarm with a cool motor; A07015 or F07016 sensor messages.
Check
Check the KTY84/PTC wiring and the sensor setting p0601.

4Thermal model settings wrong (no sensor)

Points to it
Alarm without real heating.
Check
Check the thermal model temperatures p0626–p0628 and the motor data.

Telling it apart

Relevant parameters

ParameterNameWhy it matters
p0604Motor temperature alarm thresholdA07910 above this value.
p0605Motor temperature fault thresholdF07011 above this value.
p0610Motor overtemperature response0, 1 or 2 as described above.

Evidence to collect