ControlLogix L7x T07:C40: Store Failed after download, what to check?

Question

I'm getting a Major Fault Type 7 Code 40 (Store Failed) on my ControlLogix L7x controller. This happens right after I download a project with the 'store-to-nonvolatile-memory' option selected. What should I check first?

Top answer · Written by InduQT from the fault guide and manufacturer manuals cited below · Oct 28, 2026

A Type 7 Code 40 fault on a ControlLogix controller indicates that storing the project to the nonvolatile memory card failed. This can occur during a project store operation or after a download with the store-to-nonvolatile-memory option enabled. The primary causes are a locked or failed memory card.

Likely causes and checks

1Memory card locked

Points to it
On 1756-L7x controllers, the memory card has a physical lock switch. If this switch is in the locked position, the controller cannot write to the card, causing the store operation to fail immediately.
Check
Verify the memory card's lock switch is in the unlocked position.

2Memory card failed or worn

Points to it
The memory card itself might be faulty, worn out, or incompatible if it's an old card or from another system. This can lead to repeated store failures.
Check
Try the store operation again. If it fails a second time, replace the memory card with a Rockwell-approved one.

Next check: After checking the memory card's lock switch and retrying the store, if the fault persists, consider replacing the memory card. Ensure the new card is Rockwell-approved.