Danfoss FC 302 trips A7 on ramp-down, what to check?

Question

My Danfoss FC 302 drive keeps tripping with Alarm 7 (DC Overvoltage) whenever I try to ramp down the motor, especially with heavier loads. It seems to happen only during deceleration. What should I look into first?

Top answer · Written by InduQT from the fault guide and manufacturer manuals cited below · Oct 28, 2026

Alarm 7 (DC Overvoltage) on a Danfoss VLT FC 302 indicates the DC-link voltage exceeded its limit, causing the drive to trip. This typically occurs when the motor regenerates energy back to the drive faster than it can be absorbed or dissipated, often during rapid deceleration of high-inertia loads or with overhauling loads. A supply sag can also trigger this alarm.

Likely causes and checks

1Ramp-down time is too fast for the load

Points to it
The motor is returning energy to the drive too quickly during deceleration, causing the DC-link voltage to rise above its limit. This is common with high-inertia loads.
Check
Lengthen the 3-42 Ramp 1 Ramp Down Time parameter or consider changing the ramp type to one that better manages regenerative operation. You might see Warning 5 DC Link Voltage High before the trip.

2Brake resistor is missing or inactive

Points to it
If the process requires fast stops of a heavy load, a brake resistor is needed to dissipate the regenerated energy. If it's not present or the brake function is disabled, the DC-link voltage will rise.
Check
Verify that a brake resistor is connected to the drive and check the 2-10 Brake Function parameter to ensure it is active. Warnings/Alarms 25–28 can also indicate a problem with the resistor or chopper.

3Overvoltage control is not enabled

Points to it
Without a brake resistor, the drive's internal overvoltage control might be disabled, preventing it from managing the regenerated energy effectively.
Check
Consider enabling the 2-17 Over-voltage Control parameter if no resistor is fitted. Note that Danfoss advises against enabling OVC in hoisting applications.

4Supply sag occurred

Points to it
A temporary drop in the main supply voltage can sometimes lead to an overvoltage condition in the DC link, especially if it coincides with other factors.
Check
Observe if the trip coincides with any supply disturbances rather than solely during a stop. If so, consider enabling kinetic back-up (14-10 Mains Failure) to help the drive ride through brief power sags.

Next check: First, confirm if the trip consistently happens during deceleration. If so, start by adjusting the 3-42 Ramp 1 Ramp Down Time to a longer duration. If the issue persists, check the status of any connected brake resistor and the 2-10 Brake Function parameter.

Work on fuel trains, burners, pressure vessels and electrical equipment must be done by qualified personnel following the manufacturer’s documentation and local codes. Never bypass a safety device or interlock.